Typical SG5 & 6kVA Rear Panel Layout

(Shown with Power Distribution Center )

Output Voltage & Green Mode

Select Switches

RS-232 Computer Interface

Connector

Communications Option Slot

Cover Plate

COOLING FANS

DO NOT BLOCK AIR FLOW

INPUT AC CIRCUIT BREAKER

ALWAYS TURN ON AFTER THE

BATTERY CIRCUIT BREAKER

HAS BEEN TURNED ON

BATTERY CIRCUIT BREAKER &

DISCONNECT

VERIFY THIS DISCONNECT IS IN
THE OFF POSITION WHEN:

* The UPS is being installed.
* The UPS is to be turned off or

stored for more than five days.

* Connecting external battery banks.
* Servicing the UPS.

WARNING

NEVER TURN OFF THIS

DISCONNECT WHILE THE UPS IS

OPERATING FROM UTILITY.

POWER OR DAMAGE MAY RESULT.

ALWAYS TURN OFF THE UPS

FIRST.

OUTPUT POWER DISTRIBUTION

CENTER

(see page 14)

MAINTENANCE BYPASS

SWITCH

REFER TO PAGE 20 FOR

OPERATING INSTRUCTIONS

WARNING

NEVER TURN THIS SWITCH TO

THE ON POSITION UNLESS THE

UPS HAS BEEN PLACED INTO

MANUAL BYPASS, OR THE UPS

HAS BEEN TURNED OFF

IMPORTANT

TO TURN OFF THE UPS

SWITCH THE INPUT CIRCUIT BREAKER LOCATED ON THE UPS REAR PANEL TO THE “OFF” POSITION
AND PRESS THE ON/OFF BUTTON LOCATED ON THE UPS FRONT PANEL UNTIL THE UPS BEEPS. THE
UPS WILL RUN FOR ABOUT 30 SECONDS AND SHUT DOWN. DO NOT PRESS THE ON/OFF BUTTON
OR TURN THE CIRCUIT BREAKER ON AGAIN DURING THE SHUTDOWN PROCESS OR THE UPS WILL
GO TO AN ALARM CONDITION, WARNING THAT THE UPS WAS NOT SHUT DOWN PROPERLY. SHOULD
THIS OCCUR, TURN OFF THE INPUT CIRCUIT BREAKER AGAIN AND WAIT UNTIL THE UPS SHUTS
DOWN.