Chapter 4 – Falcon SG5K-2T User Manual

Page 23

Advertising
background image

CHAPTER 4

CHAPTER 4

COMMUNICATIONS INTERFACES

RS-232 INTERFACE

21

Pin #

Function explanation

I/O

9

RS 232 Rx

INPUT

6

RS 232 Tx

OUTPUT

7

Ground

Location:

The RS-232 interface is standard on all SG series UPS models. The port is
located on the UPS rear panel, via a DB-9 female connector.

Supported Protocols

UPSILON 2000 & SEC SmartMon

BAUD RATE ------- 2400bps
DATA LENGTH---- 8 bits
STOP BIT----------- 1 bit
PARITY-------------- None

DB-9 Connector Pin Assignment

When making a connection between a computer and the UPS RS-232 port,
always use the green cable supplied with the UPS.

There are communications options that WILL DISABLE the RS-232 port and
render it inoperable. The options are as follows:

a.

Internal SNMP/HTTP agent option installed into the UPS
communications option slot.

The following options WILL NOT affect the operation of the RS-232 port:

a.

Falcon Opto Coupler based signal interface board installed in the
communications option slot.

b.

Any Falcon relay-based, dry contact signal interface board
installed in the communications option slot.

DB-9 Signals are not isolated and intended for connection to like RS-232
interfaces. DO NOT APPLY ANY OTHER VOLTAGES TO THESE PINS!