Gas piping, Controls and switches, Low gas pressure switch – John Wood SERIES 100 User Manual

Page 11: On/off switch, Caution, Hot surface igniter, Blower prover switch, Blocked outlet prover switch, Blocked inlet prover switch

Advertising
background image

11

LOW GAS PRESSURE SWITCH

(SEE FIGURE 12)

The Low Gas Switch (LGS) is a single-pole, normally open pressure switch

that will close its contacts when a rising pressure of 5.0 in. (1.25Kpa) W.C.

is encountered. The contacts will open when the pressure falls below the

fixed set point of 4.8"WC (1.18Kpa) for natural gas models and 8.5"WC

(2.08Kpa) for propane models. The LGS monitors the gas supply pressure

to the heater. If the gas supply falls below 5.0 in. (1.25Kpa) W.C., the main

burner is extinguished (if heater is running) or the heater will not start up.

ON/OFF SWITCH

The ON/OFF Switch is a single-pole, single-throw rocker switch. This switch

provides 120V from the line source to the heater.

CAUTION

THE WATER HEATER IS POLARITY SENSITIVE. BEFORE APPLYING

ELECTRICITY TO THIS HEATER BE CERTAIN THAT SUPPLY NEUTRAL

WIRE TO GROUND CHECK INDICATES ZERO VOLTAGE.

HOT SURFACE IGNITER

The Hot Surface Igniter is a device that ignites the main burner by high

temperature (>1800°F or >982°C). When 120VAC is applied to the igniter,

sufficient heat is generated to ignite the main burner. Although improvements

have been made to strengthen the igniter, it is still fragile and care must be

taken when handling the igniter to prevent breakage.

GAS PIPING

Contact your local gas service company to ensure that adequate gas service

is available and to review applicable installation codes for your area.

Size the main gas line in accordance with Table 3. The figures shown are

for straight lengths of pipe at 0.5" (125Pa) W.C. pressure drop, which is

considered normal for low pressure systems Note that fittings such as elbows

and tees will add to the pipe pressure drop.

CAUTION

DO NOT USE FLEXIBLE GAS PIPING.

TABLE 3. MAXIMUM CAPACITY OF PIPE IN CUBIC FEET

OF GAS PER HOUR

(Based upon a Pressure Drop of 0.5") Water Column and 0.6 Specific

Gravity Gas and max. gas pressure of 0.5 psig)

CONTROLS AND SWITCHES

All models are provided with four pressure switches. These switches are

essential to the safe and proper operation of the unit. All switches are wired

in series. The controller is set up to shut the unit down whenever there is a

failure of any of the switches. It is important to understand the purpose of

each switch.

FIGURE 12.

BLOWER PROVER SWITCH

(SEE FIGURE 12)

The Blower Prover Switch is provided on the heater to verify that the fan
is operating. It is a positive pressure switch whose electrical contacts are
normally open. When the fan increases the pressure in the burner, the
pressure switch will allow the electrical contacts to close. The pressure switch
is connected to the burner tap by a piece of tygon tubing. This tubing must
be connected in order for the switch to change the electrical contacts. The
controller requires that the electrical contacts on this air flow switch be open
before it will allow the blower to come on.

BLOCKED OUTLET PROVER SWITCH

(SEE FIGURE 12)

The Blocked Outlet Prover Switch is set up to shut the unit off when a build-up
of positive pressure in the exhaust vent pipe occurs. This switch is a positive
pressure switch that requires an increase in pressure to change the electrical
contacts from normally closed to open. When this switch prevents the unit
from igniting, most likely the exhaust is blocked by some means Check to
see if the condensate is allowed to flow freely from the exhaust elbow and
for obstructions in the exhaust venting and exhaust vent terminal. Also verify
that there is no more than fifty equivalent feet (15.2 m) of three inch PVC
vent pipe on the exhaust.

BLOCKED INLET PROVER SWITCH

(SEE FIGURE 12)

The Blocked Inlet Prover Switch is set up to shut the unit off when a build-up
of negative pressure in the intake vent pipe occurs. This switch is a negative
pressure switch that requires an increase in negative pressure to change the
electrical contacts from normally closed to open. The switch is connected
to the pressure tap on the PVC flange connected to the inlet of the blower.
When this switch prevents the unit from igniting, most likely the intake is
blocked by some means. Check to see if there is no more than fifty equivalent
feet (15.2 m) of three inch PVC vent pipe on the intake. Also verify that the
intake and intake vent terminal is free of obstructions that may prevent air
from entering the unit.

LENGTH

NORMAL IRON PIPE SIZES (INCHES)

IN

INPUT IN THOUSANDS BTU/HR

FEET 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2"

3"

4"

10

175 360 680 1400 2100 3960 6300 11000 23000

20

120 250 485 950 1460 2750 4360 7700 15800

30

97 200 375 770

1180 2200 3520 6250 12800

40

82 170 320 660

990 1900 3000 5300 10900

50

73 151 285 580

900 1680 2650 4750 9700

60

66 138 260 530

810 1520 2400 4300 8800

70

61 125 240 490

750 1400 2250 3900 8100

80

57 118 220 460

690 1300 2050 3700 7500

90

53 110 205 430

650 1220 1950 3450 7200

100

50 103 195 400

620 1150 1850 3250 6700

125

44

93 175 360

550 1020 1650 2950 6000

150

40

84 160 325

500 950 1500 2650 5500

175

37

77 145 300

460 850 1370 2450 5000

200

35

72 135 280

430 800 1280 2280 4600

LENGTH

NORMAL IRON PIPE SIZES (INCHES)

IN

INPUT IN KW

METERS 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2"

3"

4"

3.0

51 105 199 410

615 1160 1845 3221 6735

6.1

35

73 142 278

428 805 1277 2255 4626

9.1

28

59 110 225

346 644 1031 1830 3748

12.2

24

50

94

193

290 556 878 1552 3192

15.2

21

44

83

170

264 492 776 1391 2840

18.3

19

40

76

155

237 445 703 1259 2577

21.3

18

37

70

143

220 410 659

1142 2372

24.4

17

35

64

135

202 381 600 1083 2196

27.4

16

32

60

126

190 357 571 1010 2108

30.5

15

30

57

117

182 337 542

952 1962

38.1

13

27

51

105

161 299 483

864 1757

45.7

12

25

47

95

146 278 439

776 1610

53.3

11

23

42

88

135 249 401

717 1464

61.0

10

21

40

82

126 234 375

688 1347

Advertising
This manual is related to the following products: