* PIPE RELIEF VALVE TO OPEN DRAIN

** 140°F (60°C) TO 150°F (66°C) SHOULD BE MAXIMUM WATER

TEMPERATURE MAINTAINED IN THE PRE-HEATERS.

120°F (49°C) SHOULD BE THE MINIMUM TEMPERATURE OF WATER

IN THE PRE- HEATERS.

CONNECT CIRCULATING LINE FROM FIXTURES, IF USED, TO

COLD WATER SUPPLY LINE OF PRE-HEATER.

CONNECT CIRCULATING LINE OF 180°F (82°C) OR BOOSTED WATER,

IF USED, TO INLET WATER LINE TO BOOSTER.

INSTALL IN ACCORDANCE WITH LOCAL CODES.

TWO TEMPERATURE - TWO HEATERS (ONE PRE-HEATER/ONE BOOSTER HEATER)

WITH OR WITHOUT BUILDING RECIRCULATION

DANGER

TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE

AT FIXTURES. SEE WATER TEMPERATURE CONTROL WARNING ON

PAGE 3. IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO

OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE

FOR HOT WATER SUPPLIED TO FIXTURES.

CAUTION: IF THE PLUMBING REQUIRES

THE USE OF PIPES WITH DISSIMILAR

MATERIAL (FOR EXAMPLE, STEEL AND

COPPER), USE DIELECTRIC UNIONS TO

PREVENT AN ELECTRO-GALVANIC ACTION

BETWEEN THE PIPING COMPONENTS

WITH DISSIMILAR MATERIALS.