Adjustment procedure, Operating instructions – John Wood SERIES 100 User Manual

Page 19

Advertising
background image

19

5. Check the vent system seams and joints and ensure that there is no

discharge of flue products into the room.
6. Check the input rate.

For appliance installation locations with elevations above 6500 feet

(1982 meters) refer to HIGH ALTITUDE INSTALLATIONS section of this

manual.
a. Attach a pressure gauge (manometer) to the manifold pressure tap

(Figure 16) and refer to Table 4, page 20 for correct pressure.

b. Use this formula to “clock” the meter. Be sure other gas consuming

appliances are not operating during this interval.

3600 X H = Btuh

T
Should it be necessary to adjust the gas pressure to the burner, to obtain

the full input rate, the steps below should be followed:

T = Time in seconds to burn 1 cubic foot of gas. (With a stopwatch read

the gas meter and measure the amount of time required for the

heater to consume 1 cubic foot of gas.)

H = Heating value of gas (in Btu’s per cubic foot of gas).

Btuh = Actual heater input rate, in Btuh.

EXAMPLE: (Using (A)JWSH100199N Model)

T = 25.25 seconds

H = 1050 Btu/ft.

3

BTUH = ?

For high altitude installations, compare result to the derated input required

for the elevation at the installation location.

c. Remove the pressure regulator cover screw and adjust the pressure by

turning the adjusting screw with a small screwdriver. Do not exceed 4.0"

(1 kPa) natural gas models and 10.0" W.C. (2.5Kpa) on the propane

models.

Clockwise to increase gas pressure and input rate.

Counterclockwise to decrease gas pressure and input rate.

d. “Clock” the meter as in step (b) above.

e. Repeat steps (c) and (d) until the specified input rate is achieved.

f. Turn the manual gas valve to “OFF”. Replace the pressure regulator

cover screw. Remove the pressure gauge or manometer from the

manifold pressure tap. Replace the set screw in the manifold pressure

tap. If the gas pressure regulator cannot be adjusted to give the full

input rating with sufficient gas pressure at the valve, check to ensure

the unit is equipped with the correct orifice.

ADJUSTMENT PROCEDURE

INITIAL START-UP - (A)JWSH100199 & (A)JWSH100250

Main line gas pressure to the water heater for natural gas should be between

a maximum of 10.5" (2.59Kpa for natural gas) W.C. (14.0"/3.45Kpa for

propane) and a minimum as shown in Table 4: that is, for Natural Gas 4"

(.98Kpa) W.C. and 9.0" (1.97Kpa) for Propane Gas. The inlet gas pressure

must not exceed the maximum value. A service regulator must be installed

within 10' (305 cm) of the unit.

The (A)JWSH100199 and (A)JWSH100250 models incorporate a new gas

control, which operates at 0"W.C. (0kPa) for both natural and propane gas.

These models are configured prior to being shipped from the factory and

no adjustments are necessary prior to startup. The controller monitors the

air-flow and makes adjustments to the fan speed which in effect controls

the amount of gas flow. Therefore, the unit will self-adjust to acquire the

correct amount of input.

Once the unit is installed and filled with water and the inlet pressures

confirmed, simply turn the switch "on" and observe operation. Cycle the unit
"off" and "on" several times to ensure proper operation.

OPERATING INSTRUCTIONS

IMPORTANT

IT IS RECOMMENDED THAT A QUALIFIED SERVICE TECHNICIAN

PERFORM THE INITIAL FIRING OF THE HEATER. AT THIS TIME THE

USER SHOULD ASK THE TECHNICIAN ANY QUESTIONS IN REGARD

TO THE OPERATION AND MAINTENANCE OF THE UNIT.

CAUTION

BEFORE PROCEEDING WITH THE OPERATION OF THE UNIT, MAKE

SURE HEATER AND SYSTEM ARE FILLED WITH WATER AND ALL AIR

IS EXPELLED FROM HEATER AND PIPING.

NEVER OPERATE THE HEATER WITHOUT FIRST BEING CERTAIN IT IS

FILLED WITH WATER AND A TEMPERATURE AND A PRESSURE RELIEF

VALVE IS INSTALLED IN THE RELIEF VALVE OPENING OF THE HEATER.

DO NOT ATTEMPT TO OPERATE HEATER WITH COLD WATER INLET

VALVE CLOSED.

FILLING:
1. Close the heater drain valve.
2. Open a nearby hot water faucet to permit the air in the system to escape.
3. Fully open the cold water inlet pipe valve allowing the heater and piping

to be filled.

4. Close the hot water faucet as water starts to flow.
5. The heater is ready to be operated.

THE MAIN MANUAL GAS SHUTOFF VALVE MUST HAVE BEEN CLOSED

FOR AT LEAST FIVE (5) MINUTES. THIS WAITING PERIOD IS AN

IMPORTANT SAFETY STEP. ITS PURPOSE IS TO PERMIT GAS THAT

MIGHT HAVE ACCUMULATED IN THE COMBUSTION CHAMBER TO

CLEAR. IF YOU DETECT GAS AT THE END OF THIS PERIOD, DO NOT

PROCEED WITH LIGHTING. RECOGNIZE THAT GAS ODOR, EVEN IF

IT SEEMS WEAK, MAY INDICATE THE PRESENCE OF ACCUMULATED

GAS SOMEPLACE IN THE AREA WITH A RISK OF FIRE OR EXPLOSION.

SEE THE FRONT PAGE FOR STEPS TO BE TAKEN.

DO NOT USE THIS HEATER IF ANY PART HAS BEEN UNDER WATER.

IMMEDIATELY CALL A QUALIFIED SERVICE TECHNICIAN TO INSPECT

THE HEATER AND TO REPLACE ANY PART OF THE CONTROL SYSTEM

AND ANY GAS CONTROL WHICH HAS BEEN UNDER WATER.

LIGHT THE UNIT IN ACCORDANCE WITH THE OPERATING

INSTRUCTIONS LABEL ATTACHED TO THE HEATER.

THESE INSTRUCTIONS ARE REPEATED IN THE LIGHTING AND

OPERATING LABEL ILLUSTRATION ON PAGE 20 IN THIS MANUAL.

ADJUSTMENT PROCEDURE

INITIAL START-UP - (A)JWSH100150 MODEL

Main line gas pressure to the water heater for natural gas should be between

a maximum of 10.5" (2.59Kpa for natural gas) W.C. (14.0"/3.45Kpa for

propane) and a minimum as shown in Table 4: that is, for Natural Gas, 4.8

(1.18Kpa) W.C. and 8.5" (2.08Kpa) for Propane Gas. The inlet gas pressure

must not exceed the maximum value. A service regulator must be installed

within 10' (305 cm) of the unit.

1. Check gas line pressure with a manometer.

2. Check manifold pressure (see Table 4, page 20) using a pressure

gauge (manometer) connected to the manifold pressure tap on the

gas control valve.

If full rate adjustment is required, remove cover screw from top of the

gas control valve.

Using a small screwdriver, turn adjusting screw clockwise

to increase

or counterclockwise

to decrease gas pressure to obtain 4.0" (1 kPa)

for natural gas and 10.0" W.C. (2.5 Kpa) for L.P. Gas.

3. Cycle the burner on and off several times to check its operation.
4. Check the operation of the limit and operating controls.

3600 X 1050 = 150,000 Btuh (44 Kw)

25.25