18

ACTION:

To get to the current fault information screen, press

Menu.

DISPLAY:

ACTION:

Press the

DOWN button to highlight "current Fault" and press Select.

DISPLAY:

ACTION:

Press the

DOWN button for more information.

DISPLAY:

7. Viewing the Fault History

The controller for this water heater will store a history of ten of the last Fault

and Warning conditions that occurred. This is stored in the Fault History.

Along with all the information about the fault, including a estimate time of

when the fault occurred, information regarding the advanced diagnostics for

that fault can be accessed at any time.

ACTION:

Press the

DOWN button for more information.

DISPLAY:

ACTION:

Press the

DOWN key to scroll through the fault history. If you select a

specific fault or warning, you may press the

VIEW button to view details

regarding this fault.

DISPLAY:

8. Viewing Information About the Heater

The electronic control for this water heater monitors many different aspects

of the water to ensure safe and optimal operation. Much of the information

monitored is available to view in two areas of the control. The first is the

"Heater Status" and; the second is "Heater Information." These items can be

selected through the main menu in the same fashion as described above.

In these menus, detailed information about the water heater and the current

status of specific conditions can be found.

INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRES

ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE

FIELD INVOLVED. PLUMBING, AIR SUPPLY, VENTING, GAS SUPPLY

AND ELECTRICAL WORK ARE REQUIRED.

Before attempting start-up, thoroughly study and familiarize yourself with

the exact sequence of operation and all other details on the specific heater

being used.

The power burner is equipped with an ignition system which automatically

sequences prepurge and ignition, senses and ignites main burner flame and

sequences burner operation. Heater is equipped with an ignition control which

locks out after three unsuccessful ignition attempts. Familiarize yourself with

the sequence of operation of this unit prior to start-up.

Be certain that the water heater is full of water, that air is purged from all lines,

there are no leaks (gas and water), and all inlet water lines are open.

The following test equipment should be on hand (all test equipment must be

acclimated to ambient temperature before calibration and use.)

– Two U-tube manometers or calibrated pressure gages that can read

0-10" (0-2.5Kpa) and 0-35" (0-8.7Kpa) W.C. pressure gauges.

• Attach a gas pressure gauge or manometer to the upstream side of

main gas cock and a gas pressure gauge or manometer to the manifold

pressure tap.

• You are now ready to begin the burner start-up procedure.

PRIOR TO START UP

REQUIRED ABILITY