2

2

Pre-programming settings prior to
switchgear arrival

Entellisys provides a method for users to work on the system settings before the switchgear
arrives. Once the gear is installed and control power is applied, the saved settings can be written
to the system.

To pre-program Settings, the “Entellisys Remote HMI – User Interactive version” must be
purchased. GE will ship the Remote HMI software, System Administrator Manual (this manual),
and a System Archive when the switchgear ships from the factory.

The following steps should be performed to begin pre-programming:

• Step 1: Install the “Entellisys Remote HMI – User Interactive version” software.

See

Installing and configuring remote HMI software on page 25

for instructions.

• Step 2: Install the System Archive provided by GE.

See

Restoring an archive on page 38

for instructions.

• Step 3: Change to Offline Mode.

See

Offline mode on page 29

for instructions and for offline mode capabilities.

• Step 4: Set User Settings.

See DEH-231 Entellisys Low Voltage Switchgear System User Manual.

• Step 5: Install and Commission the Switchgear.

See

Commissioning the switchgear on page 11

for instructions.

• Step 6: Configure the System for Remote Communications.

See

Configuring the switchgear for remote communications on page 21

for instructions.

• Step 7: Write saved Settings to System.

See

Writing settings to a live system on page 33

for instructions.