APPENDIX A BLOWER PERFORMANCE TABLES

DIRECT DRIVE

CPG048 DOWN SHOT AND HORIZONTAL

SPEED TAP

EXTERNAL STATIC

PRESSURE (ESP)

in w.c.

STAN DARD

CFM

AMPS

WATTS

RPM

0. 10

1592

2.54

543

815

0. 20

1528

2.43

521

858

0. 30

1464

2.32

499

901

0. 40

1380

2.21

475

930

0. 50

1296

2.10

451

959

0. 10

1828

3.08

665

892

0. 20

1700

2.75

601

924

0. 30

1606

2.61

563

966

0. 40

1531

2.48

537

990

0. 50

1401

2.32

503

1023

0. 60

1287

2.22

477

1045

0. 70

1123

2.05

441

1073

0. 10

1926

3.34

740

937

0. 20

1825

3.18

700

965

0. 30

1712

3.03

660

989

0. 40

1598

2.87

626

1015

0. 50

1482

2.76

596

1032

0. 60

1357

2.62

564

1049

SPEED TAP

EXTERNAL STATIC

PRESSURE (ESP)

in w.c.

STAN DARD

CFM

AMPS

WATTS

RPM

0. 10

1612

2.60

554

789

0. 20

1548

2.49

532

832

0. 30

1484

2.38

510

875

0. 40

1400

2.27

486

904

0. 50

1316

2.16

462

933

0. 10

1846

3.14

676

866

0. 20

1718

2.81

612

898

0. 30

1624

2.67

574

940

0. 40

1549

2.54

548

964

0. 50

1419

2.38

514

997

0. 60

1305

2.28

488

1019

0. 70

1141

2.11

452

1047

0. 10

1954

3.43

758

924

0. 20

1853

3.27

718

952

0. 30

1740

3.12

678

976

0. 40

1626

2.96

644

1002

0. 50

1510

2.85

614

1019

0. 60

1385

2.71

582

1036

NOTES:

4 Ton models are shipped from the facto ry with speed tap set on MED.

HIGH

CPG048 DIRECT DRIVE DOWN SHOT

LOW

MED

Tables represent dry coil without filter, to co mp ensate for filter add 0.08" to measured E.S.P. SCFM
correction for wet coil = 4 %.

CPG048 DIRECT DRIVE HORIZONTAL

LOW

MED

HIGH

Advertising