APPENDIX A BLOWER PERFORMANCE TABLES

DIRECT DRIVE

CPG060 HORIZONTAL

SPEED

TAP

EXTERNAL STATIC

PRESSURE (ESP)

in w.c.

STANDAR D

CFM

AMPS

WATTS

RPM

0. 10

1416

1.63

176

588

0. 20

1295

1.61

174

621

0. 30

1200

1.68

186

660

0. 40

1133

1.79

196

704

0. 50

1045

1.90

208

753

0. 10

1543

2.00

220

627

0. 20

1485

2.12

236

671

0. 30

1425

2.20

250

698

0. 40

1352

2.26

258

748

0. 50

1304

2.39

274

786

0. 10

2107

4.02

502

797

0. 20

2031

4.13

518

819

0. 30

1980

4.27

536

858

0. 40

1954

4.37

554

880

0. 50

1887

4.48

572

913

0. 60

1839

4.58

582

940

0. 70

1782

4.72

602

968

0. 10

2224

4.73

592

832

0. 20

2165

4.79

612

860

0. 30

2123

4.91

630

891

0. 40

2079

5.01

642

913

0. 50

2029

5.14

666

946

0. 60

1978

5.26

676

969

0. 70

1926

5.38

698

1001

0. 80

1872

5.48

712

1028

0. 90

1817

5.58

722

1056

0. 10

2318

5.42

700

874

0. 20

2296

5.55

720

903

0. 30

2228

5.66

734

929

0. 40

2193

5.76

748

950

0. 50

2145

5.90

766

979

0. 60

2097

5.99

784

1012

0. 70

2054

6.10

798

1034

0. 80

1991

6.15

810

1050

0. 90

1952

6.26

826

1079

NOTES:

T5

CPG060 DIRECT DRIVE HORIZONTAL

Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM
correction for wet coil = 4 %. 5 Ton models are shipped from the factory with speed tap set on T4.

T1

T2

T3

T4

Advertising