APPENDIX A BLOWER PERFORMANCE TABLES

BELT DRIVE - HIGH STATIC HORIZONTAL

CPG036 HIGH STATIC BELT DRIVE HORIZONTAL

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

0.6

1568

0.45

1266

0.32

0.8

1492

0.47

1194

0.34

922

0.23

1.0

1476

0.52

1163

0.37

856

0.24

1.2

1458

0.57

1146

0.41

802

0.25

1.4

1458

0.63

1139

0.46

782

0.30

1.6

1139

0.52

844

0.36

1.8

844.3

0.42

CPG048 HIGH STATIC BELT DRIVE HORIZONTAL

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

0.6

1894

0.66

1585

0.49

0.8

1839

0.71

1532

0.53

1223

0.37

1

1782

0.73

1477

0.55

1170

0.39

1.2

1786

0.80

1445

0.59

1115

0.40

1.4

1764

0.86

1426

0.64

1107

0.46

1.6

1446

0.72

1098

0.50

1.8

1099

0.56

CPG060 HIGH STATIC BELT DRIVE HORIZONTAL

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

0.6

2219

0.95

1970

0.75

0.8

2215

1.04

1956

0.82

1697

0.62

1.0

2240

1.15

1957

0.90

1681

0.67

1.2

2260

1.26

1983

1.00

1683

0.74

1.4

2288

1.38

2009

1.10

1711

0.84

1.6

2032

1.21

1741

0.93

1.8

1776

1.04

CPG072 HIGH STATIC BELT DRIVE HORIZONTAL

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

CFM

BHP

0.6

2677

1.29

2486

1.07

0.8

2690

1.42

2529

1.20

2263

0.94

1.0

2740

1.60

2471

1.27

2246

1.02

1972

0.79

1.2

2748

1.74

2518

1.44

2255

1.13

1970

0.87

1.4

2797

1.87

2562

1.59

2273

1.27

2025

0.99

1.6

2556

1.67

2314

1.40

2035

1.11

1.8

2342

1.50

2037

1.21

2.0

2137

1.35

NOTE

ESP, In

H

2

O

TURNS OPEN

0

1

2

3

4

5

ESP, In

H

2

O

TURNS OPEN

0

1

2

3

4

5

ESP, In

H

2

O

TURNS OPEN

0

1

2

3

4

5

ESP, In

H

2

O

TURNS OPEN

0

1

2

3

4

5

Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P.
SCFM correction for wet coil = 4 %.