37

Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

CPG036(48)0451D SINGLE PHASE 240V/60HZ DIRECT DRIVE

2. FOR 208 VOLT TRANSFORMER OPERATION
MOVE BLACK WIRE FROM TERMINAL 3 TO
TERMINAL 2 ON TRANSFORMER.

1. REPLACEMENT WIRE MUST BE THE SAME
SIZE AND TYPE OF INSULATION AS ORIGINAL.
(USE COPPER CONDUCTOR ONLY).

AUXILIARY LIMIT SWITCH

FEMALE PLUG/CONNECTOR

INTEGRATED IGNITION CONTROL

LS

4

INSTALLER/SERVICEMAN

TO THERMOSTAT
TERMINAL BLOCK

G

R

5

7

9

IIC

Y1

W

Y2

3

6

12

10

8

11

RS

ALS

PS

PLF

C

NOTE
4

4

3

2

1

5

6

GV

C

CM

CONDENSER MOTOR

LS

LIMIT SWITCH

VENT MOTOR RELAY

VENT MOTOR

PRESSURE SWITCH

TERMINAL BLOCK (24V SIGNAL)

ROLLOUT SWITCH

VMR

VM

PS

PLF

TB1

RS

NOTES

CONTACTOR

GAS VALVE

IGNITOR

EQUIPMENT GROUND

FLAME SENSOR

EVAPORATOR MOTOR
FUSE

F

C

GV

FS
GND

IGN

IIC

EM

COMPRESSOR

COMPONENT LEGEND

COMP

ALS

TB1

TR

TRANSFORMER

HPS

LPS

LPS

LOW PRESSURE SWITCH

HPS

HIGH PRESSURE SWITCH

HIGH VOLTAGE

FACTORY WIRING

OPTIONAL
HIGH VOLTAGE

LOW VOLTAGE

FIELD WIRING

LINE VOLTAGE

LOW VOLTAGE

RD

Y1

G

R

W

NO ECONOMIZER

YL

Y/Y2

W

WH

GR

WH

WITH ECONOMIZER OPTION

C

THERMOSTAT
FIELD WIRING

BL

TB1

G

R

W

Y

C

W

STAT

BL/PK BLUE WITH PINK STRIP
YL/PK YELLOW WITH PINK STRIP

GR GREEN

WIRE CODE

BL BLUE

PU PURPLE

PK PINK

WH WHITE

BK BLACK

RD RED

BR BROWN

OR ORANGE

YL YELLOW

TB1

IIC

FS

TR

FS

F

IGN

2

1

3

3. FOR DIFFERENT THAN FACTORY SPEED TAP.
CHANGE COOLING SPEED AT COOL
TERMINAL. CHANGE HEATING SPEED AT
HEAT TERMINAL ON CONTROL BOARD

BK - HIGH SPEED

BL - MED. SPEED

RD - LOW SPEED

3 SPEED MOTOR

4. ACCESSORY ECONOMIZER PLUG ADJACENT
TO BLOWER HOUSING IN RETURN AIR
COMPARTMENT. REMOVE MALE PLUG AND
ATTACH FEMALE PLUG TO ECONOMIZER
ACCESSORY.

USE NEC CLASS 2 WIRE.

5. USE COPPER CONDUCTORS ONLY.

BLOWER CAPACITOR

BC

L2

L2

SUPPLY VOLTAGE

208-240/1/60

L1

C

T1

EM

C

R

S

H

C

CM

F

C

VM

LI

PCB

HEAT

COOL

FC

PCB

DI

RUN CAPACITOR FOR CONDENSER FAN

RCCF

STATUS LIGHT

3 BLINKS

6 BLINKS

2 BLINKS

4 BLINKS

5 BLINKS

OFF

ON

1 BLINK

OPEN AUX. LIMIT

FALSE FLAME SENSED

OUTPUT DELAY

OPEN LIMIT SWITCH

COMPRESSOR

WITHOUT INDUCER ON

PRESSURE SW ITCH

SWITCH

OPEN

OPEN ROLLOUT

SWITCH

IGNITION FAILURE

NORMAL OPERATION

NO POW ER OR

INTERNAL CONTROL

EQUIP. STATUS

OR

OR

FAULT

BAD SWITCH

AUX. LIMIT OPEN

MAIN LIMIT OPEN

BAD SWITCH

3 MIN. COMP.

PRESSURE SW ITCH

PRESSURE SW ITCH

CHECK

CHECK

GAS PRESSURE

FLAME ROLLOUT

FLAME SENSOR

GAS VALVE

GAS FLOW

CHECK

-

208-240/1/60 0140L00510 REV A

BL

Y/Y2

YL

W

Y/Y2

BL

G

RD

Y1

PK

WH

R

RD

C

R

YL

GR

Y1

G

GR

C

2 STAGE COOLING

TB1

TB1

Y

R

G

C

W

Y2

G

R

C

Y1

STAT

STAT

7. SPEED TAP TERMINATIONS SHOWN ON
DIAGRAM ARE REPRESENTATIVE, BUT ACTUAL
FACTORY SETTING MAY BE DIFFERENT BASED
ON HEATING VALUE AND CAPACITY OF UNIT.

6. PURPLE WIRE CONNECTS TO TRANSFORMER
(PIN 1).

SEE UNIT RATING PLATE FOR TYPE AND SIZE OF
OVERCURRENT PROTECTION.

8. TO RUN DIFFERENT SPEED FOR HEATING AND
COOLING, DISCONNECT GEEEN JUMPER FROM
"COOL" TERMINAL AND REPLACE WITH
APPROPRIATE SPEED TAP. THEN PLACE
DISCONNECTED END OF JUMPER ON
"UNUSED" TERMINAL LEFT OPEN BY MOVING
THE SPEED TAP.