Control panel, Galaxy pw – MGE UPS Systems Galaxy PW User Manual

Page 20

Advertising
background image

12

"Load" light 5

light off: load not supplied;

light shines green: load supplied via the

inverter or the bypass AC source (via the
static bypass).

Buzzer 6

The buzzer sounds in the following situa-
tions:

load supplied by the bypass AC source;

load on battery;

operating problems.

It sounds slowly and discontinuously for a
minor problem or when the inverter is on
battery power.
When the alarm "LOW BATTERY SHUT-
DOWN" is activated, the buzzer sounds
more rapidly. Finally, if the inverter shuts
down, the beep is loud and continuous.
The buzzer may be reset by pressing a
button. If the buzzer is reset, a higher
level alarm will set it off again.

"Inverter ON" button 7

This button is used to start the inverter
locally.

"Inverter OFF" button 8

This button turns the inverter off locally.

Keys 9 and 10

These keys are used to select commands
in the main menu and access the sec-
ondary messages.

Key 11

This key is used to validate the user’s
choice.

Key 12

This key is used to access the main
menu: display language, display-contrast
setting, sound level of the buzzer, lamp
test, date and time settings, inverse-video
and event log.

"V" key 13

This key is used to access voltage mea-
surements:

normal AC source phase-to-phase volt-

ages;

bypass AC source phase-to-phase and

phase-to-neutral voltages;

load phase-to-phase and phase-to-neu-

tral voltages.

"A" key 14

This key is used to access current mea-
surements:

normal AC source, bypass AC source

and load currents;

percent load;

load crest factor.

"W.Hz" key 15

This key is used to access other measure-
ments:

normal AC source, bypass AC source

and inverter frequencies;

level of active and apparent power

drawn by the load;

load power factor;

inverter load level (percent).

"Anomaly" indicator light 16

This indicator light indicates the presence
of anomalies.

key 17

This key is used to access the primary
messages.

"Battery" key 18

This key is used to access battery mea-
surements:

battery voltage (or the DC voltage on

frequency converters without a battery);

battery current (charge or discharge);

battery temperature;

available battery backup time;

inverter load level (percent).

"Forced-transfer" key 19

This key is used to voluntarily transfer the
load to the inverter or from the inverter to
the static bypass (return transfer). Transfer
and return transfer are carried out only fol-
lowing confirmation requested by the sys-
tem display and a warning as to the risk of
an interruption in the supply of power to
the load.

"Alarm reset" key 20

This key is used to reset stored alarms.
The system accepts resetting only when
alarms have been cleared.

"Buzzer reset" key 21

This key is used to stop the buzzer.
However, new alarms set the buzzer off
again.

Display 22

The display continuously indicates the
system operating status.

Control Panel

Galaxy PW

TM

100 to 225 kVA