Shutdown of the inverter, Shutdown of a rectifier/charger, Shutdown – MGE UPS Systems Galaxy PW User Manual

Page 22: Galaxy pw

Advertising
background image

14

shutdown of the inverter

press the "inverter OFF" button 8 on

the control panel for three seconds (see
figure 19).

single-UPS unit

the green "inverter" light 4 on the con-

trol panel goes off;

the green "static-bypass" light 3 goes

on;

the inverter stops;

if bypass AC source (Mains 2) transfer

conditions are satisfied, the inverter shuts
down and the load is transferred to the
bypass AC source;

if bypass AC source (Mains 2) transfer

conditions are not satisfied, the inverter
does not shut down. The message
"MAINS 2 OUTSIDE TOLERANCES,
TRANSFER DISABLED" is displayed.

parallel UPS unit

if the system is redundant, i.e. the other

parallel-connected inverters can supply
the load on their own, the inverter shuts
down and the green "inverter" light 4
goes off.
The load is not affected in that the other
inverters continue to supply it normally;

if the system is not redundant, the other

inverters go to overload status.
If overload conditions are overrun, the
load is transferred to the bypass AC
source:

the green lights 3 turn green,

the green "inverter" light 4 goes off.

shutdown of a
rectifier/charger

It is recommended not to stop the rectifi-
er/charger because the battery will no
longer be charged. Except in the case of a
test of the inverter on battery power, the
rectifier/charger should be shutdown after
the inverter to avoid unnecessary battery
discharge.
Proceed in the following order:

open battery circuit breaker QF1;

open normal AC input circuit breaker

Q1:

the rectifier/charger shuts down,

the green "rectifier/charger" light 1

goes off.

Shutdown

shutdown

Galaxy PW

TM