Maintenance, Parallel ups redundant and for increased output, User’s manual – MGE UPS Systems Galaxy PW User Manual

Page 37

Advertising
background image

29

parallel UPS redundant and
for increased output

See figure 22.

isolate all UPSs

Proceed in the following order (see figure
23):

shut down the inverters (press the

"inverter OFF" buttons 8 for three sec-
onds),

close switch Q3BP and open switch

Q5N in the external bypass unit,

open switches Q1, QF1 and Q5N on the

UPS units.

start-up

Following servicing, proceed in the follow-
ing order (see figure 24):

close switches Q5N on the UPS units,

close switch in the external bypass unit,

open switch Q3BP in the parallel-con-

nection unit,

close switches Q1 and QF1 on the UPS

units,

start the inverters (press the "inverter

ON" buttons 7 ).

NOTE

We recommend that you
call on the after-sales
support department to
carry out these opera-
tions.
Note that for parallel
UPSs for increased out-
put, the entire installation
must be bypassed
because it is not possible
to isolate just one UPS
unit.

Maintenance

Fig. 24

Fig. 23

Fig. 22

2

3

4

5

1

0

1

0

1

0

1

0

Q5N

Q3BP

Q5N

Q1

Q4S

QF1

0

I

external bypass

7

5

6

1

Galaxy PW

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

2

3

4

5

1

0

1

0

1

0

1

0

Q5N

Q3BP

Q5N

Q1

Q4S

QF1

0

I

external bypass

7

5

6

1

Galaxy PW

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

2

1

Q3BP

Galaxy 1

Galaxy 2

2

1

Galaxy 3

2

1

Galaxy 4

2

Q5N

1

2

Q1

QF1

Q5N

Q4S

User’s Manual

Advertising