Start-up, System start-up, Start-up of a module – MGE UPS Systems Galaxy PW User Manual

Page 21: Single-ups unit or redundant parallel ups, Parallel ups unit for increased output, Start-up of a rectifier/charger, Start-up of an inverter, User’s manual

Advertising
background image

13

system start-up

single-UPS unit or redundant
parallel UPS

See figure 15.
Proceed in the following order:

close the upstream switches supplying

normal and bypass AC source power (on
the LV switchboard);

close normal AC input switch Q1. The

system powers up:

the rectifier/charger automatically starts,

green light 1 on the control panel goes

on,

light 2 turns red;

close bypass AC input switch Q4S:

green lights 3 and 5 on the control

panel go on;

close inverter output switch Q5N;

close battery circuit breaker QF1;

light 2 goes off;

open maintenance bypass switch

Q3BP;

press the "inverter on" button 7 on the

control panel:

the green "inverter" light 4 flashes,

the inverter starts, then, if the bypass AC

source transfer conditions are satisfied,
the load is transferred to the inverter if the
on-line mode is selected.

the green "static-bypass" light 3 goes

off,

the green "inverter" light 4 shines for

on-line mode.

parallel UPS unit for
increased output

See figure 16.
Proceed in the following order:

check that all load devices are off or

that the load is disconnected;

close the upstream switch supplying

normal AC source power (on the LV
switchboard);

close the normal AC input circuit break-

ers Q1 on the UPS units. The system
powers up:

the rectifier/chargers automatically start,

the green "rectifier/charger" lights 1 in

the control panels go on,

lights 2 turn red;

close the battery circuit breakers QF1;

lights 2 go off;

green lights 3 and 5 on the control

panels go on;

close output switches Q5N for the

inverters and in the external bypass unit;

open maintenance bypass switch Q3BP

in the external bypass unit;

press the "inverter on" button 7 on

each control panel:

the green "inverter" lights 4 flash;

when a sufficient number of inverters

are ready, the inverter-output contactors
close:

the green "inverter" lights 4 shine per-

manently green;

the "static-bypass" lights 3 go off.

start-up of a module

start-up of a rectifier/charger

rectifier/charger start-up is automatic

when the normal AC input circuit breaker
Q1 is closed:

the green "rectifier/charger" light 1 on

the control panel goes on;

close battery circuit breaker QF1.

start-up of an inverter

When the rectifier/charger is on:

press the "inverter ON" button 7 on the

control panel;

the green "inverter" light 4 flashes.

Single-UPS unit

the inverter starts, then, if the bypass

AC source transfer conditions are satis-
fied, the load is transferred to the inverter
if the on-line mode is selected. For on-
line mode:

the green "inverter" light 4 remains on,

the "static-bypass" light 3 goes off.

Parallel UPS unit

the inverter starts and awaits the start of

the other inverters;

when they are all on or enough have

been started to supply the rated load
power, the output switch for each running
inverter closes and the load is supplied
with power:

the green "static-bypass" light 3 goes

off,

the green "inverter" light 4 on the con-

trol panels of the running inverters goes
on.

WARNING

Rectifier/charger start-up
is automatic when normal
AC input circuit breaker
Q1 is closed. DC voltage
is present in the DC bus.

start-up

Start-up

Fig. 16

Fig. 15

Q5N

Q1

Q4S

QF1

0

I

3

1

2

1

0

1

0

1

0

1

0

1

0

Q3BP

1

0

1

0

1

0

1

0

1

0

1

0

1

0

5

4

6

1

0

1

0

1

0

1

0

3

1

2

1

0

1

0

4

Q5N

Q1

Q5N

Q1

QF1

0

I

1

0

1

0

User’s Manual

Advertising