Alarms, General, Maintenance bypass – MGE UPS Systems Galaxy PW User Manual

Page 30

Advertising
background image

22

general

The auto diagnostic system considers any
system status other than normal as a
problem.
Before taking any action, note down the
messages displayed on the control panel.
Certain problems may prevent the control
panel from functioning.
In this case, it is strongly recommend-
ed to call the MGE UPS SYSTEMS after-
sales support department.

If the load is still correctly supplied with

power, it has probably been transferred to
the bypass AC source (static bypass) and
is therefore no longer protected (if the sys-
tem is in on-line mode);

if the load is no longer supplied with

power, transfer it manually to the mainte-
nance bypass (see section below).

maintenance bypass

This operation is possible only if the sys-
tem includes a bypass AC source. It
results in the load being directly supplied
by the bypass AC source via maintenance
bypass switch Q3BP, thus ensuring a
higher level of security in the event of a
malfunction.
Switching procedures are explained on
drawings next to each switch in the UPS
cabinet and the external bypass unit. See
section "maintenance configuration".

Alarms

alarms

Galaxy PW

TM

100 to 225 kVA

Advertising