Installation – MGE UPS Systems Comet EX 11 RT 3:1 User Manual

Page 20

Advertising
background image

Page 20 -

34007724EN/AA

2. Installation

2.6 Required protective devices and cable cross-sections

Recommended upstream protection

Recommended downstream protection

The indicated protection ensures
discrimination for each output circuit
downstream of the UPS, whether supplied
by the Normal or the Bypass AC source.
If these recommendations are not followed,
protection discrimination is not achieved and
may result in a potential power interruption
to the connected devices.

Required cable cross-sections

Terminal-block cable capacity: 10 mm

2

, solid or stranded wire (maximum 13 mm

2

or AWG 6).

Capacity for earthing conductor: 10 mm

2

, solid or stranded wire (maximum 13 mm

2

or AWG 6).

Note: see the simplified diagrams in the appendix for common or separate AC inputs, indicating the positions of the
protection devices, the characteristics of the internal UPS fuses and UPS line currents under overload conditions.

Note: see the simplified diagrams in the appendix for common or separate AC inputs, indicating the positions of the
protection devices, the characteristics of the internal UPS fuses and UPS line currents under overload conditions.

Downstream

circuit breaker

Z curve - 10A

C curve - 4A

Z curve - 10A

C curve - 4A

Z curve - 10A

C curve - 6A

UPS power

rating

5 kVA

7 kVA

11 kVA

Common AC inputs

Upstream circuit-breaker

Normal / Bypass AC sources

D curve - 40A

D curve - 40A

D curve - 63A

UPS

power

rating

5 kVA

7 kVA

11 kVA

Upstream circuit-breaker

Normal AC source

C curve - 32A

C curve - 32A

C curve - 63A

Separate AC inputs

Upstream circuit-breaker

Bypass AC source

D curve - 40A

D curve - 40A

D curve - 63A