Comet EX Transformer

Nominal power

Nominal current

Input voltage

Voltage drop

Frequency

Isolation (EN 61558-1-2-4)

Operating temperature

Max. operating rel. humidity

Derating / altitude

Dimensions HxWxD (tower)

Dimensions HxWxD (rack 3U)

Weight

11 kVA

63 A

160-280 Volts AC

7 Volts at nominal load

50/60 Hz (+/-10%)

3.75 kV / 5 M ohms

From 0° to +40°C

95%

Pn-10% > 1000 m

444 x 131 x 635 mm

131 x 444 x 635 mm

86.5 kg

Permissible UPS overloads as a function of time

UPS Input / output characteristics

Voltage

320 to 465 Volts AC

187 to 264 Volts AC*

230 Volts AC (200/208/220/240/250 V are

possible values)

Source

Normal AC source

Bypass AC source

Load output

Frequency

40 to 70 Hz

48 to 52 Hz**

50/60 Hz autoranging

(or frequency converter)

(*): depends on output voltage setting, can be modified by software.
(**): set to +/- 4% by default, (1,2,4,8 are possible values), can be modified by software.

Power supplied as a function of input voltage

5. Appendices

Short-circuit current provided by the UPS in Normal or Batterie mode

Comet EX 5 RT : 110 A for 80 ms.

Comet EX 7 RT : 110 A for 80 ms.

Comet EX 11 RT : 150 A for 80 ms.

P/Pn

1.02

0.5s

t

30s

1.1

1.25

1.5

60s

120s

P/Pn

100%

70%

250V

U

320V

465V