UPS SET UP
EXIT ENT

19

OFF

ON

3. Operation

3.1 Initial start up

Check that the manual bypass switch 7 is on Normal position.
Set the normal AC source circuit-breaker 9 to the "I" position.
Set the battery circuit breaker 12 to the "I" position.

The load is powered via the bypass AC source, but not protected
by the UPS.
Batteries are recharging, an eight-hour recharge period is
necessary to get full backup time.
LED 15 is ON.

15

PRESS ON

TO START UPS

If specific settings are required, it is recommended to enter the UPS personnalisation mode at this stage.
It is possible to enter this mode through the front panel buttons or the Personal Solution-Pac software for Windows
included in the MGE UPS SYSTEMS Solution-Pac power management suite CD-ROM.

Accessing personalisation with front panel buttons

Press "scroll up" 19 and "scroll down" 20 function buttons together

for more than 3 seconds.

Press the function button 20 placed under the ENT word to enter the

set up mode and follow the LCD messages using the buttons now
defined as select keys.

Local settings

Factory setting

English

International format

(DD-MM-YYYY/HH:MM)

Time in France

Quick beeps

Function

Language

Date / time format

Date / time change

Audible alarm

Options

French, Spanish, German, Italian.

US format (MM-DD-YYYY/HH:MM AM/PM).

MM-DD-YYYY/HH:MM adjustable.

Slow beeps.

Output features

Factory setting

230 Volts AC

Disabled

Auto ranging

Disabled

Disabled

Industrial

If the Bypass AC source is

out of tolerances

10 ms

102%

Function

Output voltage

Frequency converter

Output frequency

Eco mode

Hot standby

Operating mode

Transfer on Bypass AC

source

Break time

Overload level

Options

200/208/220/240/250

Enabled

50/60 Hz

Enabled

Enabled

I/T Network

If the Bypass AC source is

inside tolerances

10 to 200 ms

(by steps of 10 ms)

50/70%

Comments

Bypass AC source disabled.

User selectable under frequency converter

mode.

See glossary.

N+1 redundancy

(See section 2.5 "Hot standby").

(*)

(*)

Break time calibration during load transfer

on Bypass AC source out of tolerances.

(*) : - Select "I/T Network" and "AC Bypass within tolerance" for computer loads.

- Select "Industrial" and "AC Bypass out of tolerance" in case of absolute need for service continuity (with potential
10 ms break).