3.6 Shut down

1 - Press the OFF button 18 more than 3 seconds.

The load is no longer protected by the UPS. It is powered
via the bypass AC source. If the UPS is set in frequency
converter mode, the load will not be powered.
If the bypass AC source is out of tolerance, the UPS will
generate a 10 ms output calibrated break.

2 - Set the battery circuit breaker(s) 12 to the "0" position.
3 - Set the Normal AC source circuit-breaker 9 to the "0" position.
4 - For a full shutdown of UPS and connected load, the upstream circuit
breaker (not included) should be set to the "0" position.

15

LOAD LEVEL

4 kW / 5 kVA

3. Operation