2. Installation

Connection of battery cables

1 - Check that the battery circuit breaker 12
is OFF ("0" position),
2 - Connect the battery power cable 28 to
the connectors 6 of the power and battery
modules,
3 - Connect the battery detection cable 29
to the connectors 4 of the power and
battery modules,

28

6

4

29

Connection of galvanic isolation transformer

Output cable cross-section (not provided): 10 mm

2

, solid or stranded wire (maximum 13 mm

2

or AWG 6).

Input cable cross-section (not provided): 10 mm

2

, solid or stranded wire (maximum 13 mm

2

or AWG 6).

Transformer Input

Transformer Output