Operation, 2 final start up sequence – MGE UPS Systems Comet EX 11 RT 3:1 User Manual

Page 27

Advertising
background image

34007724EN/AA

- Page 27

3. Operation

ON/OFF features

Factory setting

Disabled

Enabled

Enabled

Disabled

Enabled

Function

Cold start

Forced reboot

Automatic restart

Sleep mode

UPS ON/OFF by software

Options

Enabled

Disabled

Disabled

Enabled

Disabled

Comments

Start on battery.

Enables automatic restart of the system even

if normal AC source is restored before the end

of the shutdown sequence.

UPS restarts automatically

when normal AC source is restored.

Automatic shudown on battery if output load

level < 10%.

Enables consideration of shutdown or restart

orders from software to be authorized.

Battery features

Factory setting

Every week

20%

UPS reads # of battery

modules connected

Enabled

Function

Battery test

Low battery signal

Run time choice

Battery deep discharge

protection

Options

No test / daily / monthly

0 to 100%

From 50 to 400 Ah

Disabled

Comments

1% increment.

Requires Comet EX RT CLA if using options

(see section 1.4 "Battery extensions").

If disabled, lost of

MGE UPS SYSTEMS warranty.

Use EXIT key when set up is completed.

These parameters are only adjustable if UPS is OFF.

Access to the personalisation through external software

Insert the Solution-Pac CD ROM in your CD drive.

At the first Navigator Screen, select "Installation" and follow the instructions to install Personal Solution-Pac for

Windows.

If nothing appears, launch startup.exe

Then go to "Advanced settings" and "UPS settings".

Please note that the Linux/Unix/MacOS versions of Personal Solution-Pac do not include this feature.

3.2 Final start up sequence

Press the ON button more than 3 seconds.

After UPS internal test sequence, the green LED 13 goes on.

During the restart, if the Bypass AC source is out of tolerance, the UPS will generate an output 10 ms calibrated
break.