Eps 6000 ups shared systems, 2 — 10 operation – MGE UPS Systems EPS 6000 User Manual

Page 36

Advertising
background image

B: Rectifier/charger on

This green LED indicates that the rectifier/battery charger is on.

C: Rectifier/charger fault

This red LED indicates an alarm condition within the rectifier/battery charger. it
indicates the presence of one of the following fault conditions:

Input circuit breaker Q1 open

Input power protection fuse blown

Rectifier/battery charger over-temperature

Battery charge overcurrent

Battery overvoltage

Rectifier/battery charger control board fault

Power supply board fault

D: Main AC input (mains 1) outside tolerance

This orange LED indicates that the main AC input (mains 1) source is outside
tolerance (voltage and/or frequency too high or too low).

E: Reserved for future use.

F: Battery temperature outside tolerance

This orange LED indicates that the ambient temperature of the battery is
too high or too low.

G: Battery charging

This orange LED indicates that the battery is being recharged. This LED functions
only when the connected battery is of the vented lead-acid type (sealed lead-acid
batteries will not activate this signal).

H: Inverter fault

This red LED indicates an alarm condition in the inverter, which may be one or
more of the following conditions:

Inverter shutdown due to output voltage out of tolerance

Inverter output protection fuse blown

Inverter leg fault

Inverter output transformer over-temperature

Inverter leg over-temperature

Current sharing fault

Internal clock fault

Inverter control board fault

Power supply board fault

I:

Battery discharged

This orange LED indicates that the battery has reached the end of its autonomy,
shutting down the inverter.

2 — 10

Operation

EPS 6000 UPS Shared Systems