Figure, Eps 6000 ups shared systems, 2 — 22 operation – MGE UPS Systems EPS 6000 User Manual

Page 48: Ups bypass ups bypass

Advertising
background image

Figure

E P S 6 0 0 0 M a j o r I n t e r n a l C o m p o n e n t s ,

2-17

S t a t i c S w i t c h C a b i n e t ( S S C )

In the UPS modules:

Q1

Input isolation circuit breaker, used to isolate the UPS module from the main
AC input (mains 1) source and provide input current protection.

Q5N

UPS isolation circuit breaker, used to isolate the UPS module from he attached load.

K3N

Inverter output contactor (automatic), used to isolate the inverter when it is off.

In the circuit of the battery of each UPS module:

QF1

Battery disconnect circuit breaker, used to disconnect the battery from the UPS. QF1
provides isolation and protection between the UPS module and its battery system.

UPS

BYPASS

UPS

BYPASS

FUSES

(F1, F2, F3, & F4)

ROTARY SWITCHES

(SW1, & SW2)

PCA (EPOZ)

PCA (ACOZ)

PCA (RAUZ)

PCA (ACPZ)

PCA (OBEZ)

CAPACITORS

(C11, C12, & C13)

FAR SIDE OF PANEL

PCA (IBEZ)

CARD CAGE

TRANSFORMER (T12)

CIRCUIT BREAKER
(Q2S)

FUSES (F11, F12, & F13)

FAR SIDE OF PANEL

STATIC SWITCH

STATIC SWITCH PCA
(SSSZ)

PCA (GTCZ)

PCA (SRIZ)

PCA (AROZ)

PCA (ALEZ)

CIRCUIT BREAKER
(Q3BP)

CIRCUIT BREAKER
(Q5N)

STATIC SWITCH CABINET

(WITH FRONT DOORS REMOVED)

MAINTENANCE BYPASS CABINET

(WITH FRONT DOOR REMOVED)

PCA (PROZ)

PCA (CBOZ)

TRANSFORMER (T13)

FAR SIDE OF PANEL

2 — 22

Operation

EPS 6000 UPS Shared Systems