3 specification, 1 general specification, Melsec-a – MITSUBISHI ELECTRIC AJ65SBT-64AD User Manual

Page 16: 33 specification, Table 3.1 general specification

Advertising
background image

3 - 1

MELSEC-A

3 SPECIFICATION

3

3 SPECIFICATION

This chapter provides the specifications of the AJ65SBT-64AD.

3.1 General Specification

Table 3.1 indicates the general specifications of the AJ65SBT-64AD.

Table 3.1 General specification

Item

Specification

Usage ambient temperature

0 to 55°C

Storage ambient temperature

-20 to 75°C

Usage ambient humidity

10 to 90%RH, no condensation

Storage ambient humidity

10 to 90%RH, no condensation

When there is intermittent vibration

Frequency

Acceleration

Amplitude

Sweep count

10 to 57Hz

0.075mm

(0.0030inch)

57 to 150Hz

9.8m/s

2

When there is continuous vibration

Frequency

Acceleration

Amplitude

10 to 57Hz

0.035mm

(0.0013inch)

Vibration durability

Conforming to JIS B

3501, IEC 1131-2

57 to 150Hz

4.9m/s

2

10 times in each direction

X, Y, Z (80 minutes)

Shock durability

Conforming to JIS B 3501, IEC1131-2 (147m/s

2

, 3 times each in 3 directions)

Usage environment

No corrosive gas

Usage height

Less than 2000 m (less than 6562 ft.)

Installation area

Within the control board

Over-voltage category *

1

Less than II

Pollution level *

2

Less than 2

*1 Indicates the location where the device is connected from the public cable network to the device structure wiring

area.

Category II applies to the devices to which the power is supplied from a fixed equipment.

Surge withstand voltage for devices with up to 300V of rated voltage is 2500V.

*2 This is an index which indicates the degree of conductive object generation in the environment Pollution level 2 is

when only non-conductive pollution occurs.

A temporary conductivity caused by condensation must be expected occasionally.