Melsec-a, 4 setup and preparation before operation – MITSUBISHI ELECTRIC AJ65SBT-64AD User Manual

Page 35

Advertising
background image

4 - 4

MELSEC-A

4 SETUP AND PREPARATION BEFORE OPERATION

Number

Name and

appearance

Description

Use the switches in STATION NO. "10", "20" and "40" to set the tens of the station number.

Use the switches in STATION NO. "1", "2", "4" and "8" to set the units of the station number.

The switches are all factory-set to OFF.

Always set the station number within the range 1 to 64.

Setting any other number than 1 to 64 will result in an error, flickering the "L ERR." LED.

You cannot set the same station number to two or more stations.

Tens

Units

Station

Number

40

20

10

8

4

2

1

1

OFF

OFF

OFF

OFF

OFF

OFF

ON

2

OFF

OFF

OFF

OFF

OFF

ON

OFF

3

OFF

OFF

OFF

OFF

OFF

ON

ON

4

OFF

OFF

OFF

OFF

ON

OFF

OFF

10

OFF

OFF

ON

OFF

OFF

OFF

OFF

11

OFF

OFF

ON

OFF

OFF

OFF

ON

64

ON

ON

OFF

OFF

ON

OFF

OFF

(Example) To set the station number to "32", set the switches as indicated below.

Tens

Units

Station

Number

40

20

10

8

4

2

1

32

OFF

ON

ON

OFF

OFF

ON

OFF

4)

Station number

setting switches

Setting Switches

Set Value

4

2

1

Transmission

Speed

0

OFF

OFF

OFF

156kbps

1

OFF

OFF

ON

625kbps

2

OFF

ON

OFF

2.5Mbps

3

OFF

ON

ON

5.0Mbps

4

ON

OFF

OFF

10Mbps

5)

Transmission

speed setting

switches

Always set the transmission speed within the above range.

The switches are all factory-set to OFF.

Making any other setting than the above will result in an error, flickering the "L ERR." LED.

6)

Terminal block

Used to connect the module power supply, transmission and I/O signals.

7)

DIN rail hook

Used to mount the module to the DIN rail.

Advertising