3 - 15

MELSEC-A

3 SPECIFICATION

3.6.3 Input range setting (Address RWwm+1)

(1) Set the analog input range per channel.

(2) Operation is performed according to the setting made for the leading edges of the

initial data setting request flag (RY(n+1)9).

(3) The default setting is -10 to +10V for all channels.

b15

b12

b11

b8

b7

b4

b3

b0

to

CH.4

to

CH.3

to

CH.2

to

CH.1

Input Range

Set Value

-10 to +10V

0H

0 to 5V

1H

1 to 5V

2H

0 to 20mA

3H

4 to 20mA

4H

User range setting 1 (-10 to +10V)

5H

User range setting 2 (0 to 5V)

6H

User range setting 3 (0 to 20mA)

7H

(4) When making offset/gain setting, set all channels to any of "user range settings 1

to 3".

Setting any other range will result in an error and flicker the "RUN" LED at 0.1s

intervals.