5 - 7

MELSEC-A

5 PROGRAMMING

5.2.2 Program examples for use of the ACPU/QCPU (A mode) (dedicated instructions)

The program examples in this section are created under the following conditions.

A sequence program is used to set the network and automatic refresh parameters.

[Relationships between PLC CPU, master module and AJ65SBT-64AD]

PLC CPU

Device X

Device Y

Device D

X100 to X10F

X110 to X11F

Y100 to Y10F

Y110 to Y11F

D200

D201

D202

D203

Device D

D456

D457

D458

D459

Master module

Address

Remote input (RX)

RX00 to RX0F

RX10 to RX1F

E0

H

E1

H

Remote output (RY)

RY00 to RY0F

RY10 to RY1F

160

H

161

H

Remote register (RWw)

RWw0

RWw1

RWw2

RWw3

1E0

H

1E1

H

1E2

H

1E3

H

Remote register (RWr)

RWr0

RWr1

RWr2

RWr3

2E0

H

2E1

H

2E2

H

2E3

H

AJ65SBT-64AD

(Station number 1)

Remote input (RX)

RX00 to RX0F

RX10 to RX1F

Remote output (RY)

RY00 to RY0F

RY10 to RY1F

Remote register (RWw)

RWw (A/D conversion
enable/prohibit specification)

RWw2 (Moving average processing
count setting)

RWw3 (Reserved)

RWw1 (Input range setting)

Remote register (RWr)

RWr (CH.1 digital output value)

RWr2 (CH.3 digital output value)

RWr3 (CH.4 digital output value)

RWr1 (CH.2 digital output value)

[Initial settings]

A/D conversion enabled channels .................Channels 1, 2

Moving average processing channel.............Channel 2 count setting = 16 times

Input range setting .........................................Channel 1: 0 to 5V

Channel 2: User range setting 1