2 current input characteristics, Melsec-a, Fig. 3.2 current input characteristic point – MITSUBISHI ELECTRIC AJ65SBT-64AD User Manual

Page 20

Advertising
background image

3 - 5

MELSEC-A

3 SPECIFICATION

3.3.2 Current input characteristics

The current input characteristic graph is shown below.

2

1

4095

4000

2000

-2000

-4000

0

4

-30

-20

-10

0

10

20

30

Analog input current (mA)

Analog input

parcitcal value

-96

Di

gi

ta

l out

put

val

u

e

Number

Analog Input Range

Setting

Offset

Value

Gain

Value

Digital Output

Value*

Maximum

Resolution

1)

0 to 20mA

0mA

20mA

5µA

2)

4 to 20mA

4mA

20mA

User range setting 3

(0 to 20mA)

0mA

20mA

0 to 4000

4µA

Fig. 3.2 Current Input Characteristic

POINT

(1) Do not input more than ±30mA. A breakdown may result due to heat increase.
(2) If the analog input provided corresponds to the digital output value* beyond its

range, the digital output value is fixed to the maximum or minimum.

For 0 to 4000, the digital output value is within the range -96 to 4095.

(3) Within the analog input and digital output scopes of each input range, the

maximum resolution and accuracy are within the performance specification
range. Outside those scopes, however, they may not fall within the performance
specification range. (Avoid using the dotted line part in Fig. 3.2.)

(4) Set the offset and gain values of the user range setting within the range

satisfying the following conditions.
(a) Setting range when user range setting 3 is selected: 0 to 20mA
(b) (Gain value) > (Offset value)

If you attempt to make setting outside the setting range of (a), the "RUN" LED
flickers at 0.5s intervals.
Set the values within the setting range.
If you attempt to make setting outside the setting range of (b), the "RUN" LED
flickers at 0.5s intervals.
Make setting again.

Advertising