4 function list, Melsec-a, 3 specification 3.4 function list – MITSUBISHI ELECTRIC AJ65SBT-64AD User Manual

Page 23

Advertising
background image

3 - 8

MELSEC-A

3 SPECIFICATION

3.4 Function List

The AJ65SBT-64AD function list is shown in table 3.3.

Table 3.3 AJ65SBT-64AD function list

Item

Description

Refer to

Sampling processing

Perform A/D conversion of an analog input value one by one and store the result into

the remote register each time.

Section 3.4.1

Section 3.5.2

Moving average

processing

Average the digital output values of the specified count measured per sampling time.

Section 3.4.2

Section 3.5.2

Section 3.6.4

A/D conversion

enable/prohibit

specification

Specify whether A/D conversion is enabled or disabled per channel.

By prohibiting the conversion for the channels which are not used, the sampling time

can be shortened.

Section 3.6.2

Can set the analog input range per channel to change the I/O conversion

characteristics.

Select the input range setting from among the following 8 types.

Input Range

Set Value

-10 to +10V

0H

0 to 5V

1H

1 to 5V

2H

0 to 20mA

3H

4 to 20mA

4H

User range setting 1 (-10 to +10V)

5H

User range setting 2 (0 to 5V)

6H

User range setting 3 (0 to 20mA)

7H

Input range changing

function

Section 3.6.3

Offset/gain setting

The offset/gain setting can be performed volumeless for each channel, and the I/O

conversion characteristics can be changed.

Section 4.4

Advertising