1 voltage input characteristics, Melsec-a, Fig. 3.1 voltage input characteristic point – MITSUBISHI ELECTRIC AJ65SBT-64AD User Manual

Page 19

Advertising
background image

3 - 4

MELSEC-A

3 SPECIFICATION

3.3.1 Voltage input characteristics

The voltage input characteristic graph is shown below.

3

2

1

4095

4000

2000

-2000

-4000

-4096

0

1

-15

-10

-5

0

5

10

15

Analog input voltage (V)

Analog input parcitcal value

-96

Di

g

it

a

l out

pu

t va

lu

e

Number

Analog Input Range

Setting

Offset

Value

Gain

Value

Digital Output

Value*

Maximum

Resolution

1)

-10 to +10V

0V

10V

-4000 to +4000

2.5mV

2)

0 to 5V

0V

5V

1.25mV

3)

1 to 5V

1V

5V

0 to 4000

1.0mV

User range setting 1

(-10 to +10V)

0V

10V

-4000 to +4000

2.5mV

User range setting 2

(0 to 5V)

0V

5V

0 to 4000

1.0mV

Fig. 3.1 Voltage Input Characteristic

POINT

(1) Do not input more than ±15V. The element may be damaged.
(2) If the analog input provided corresponds to the digital output value* beyond its

range, the digital output value is fixed to the maximum or minimum.

For 0 to 4000, the digital output value is within the range -96 to 4095.
For -4000 to +4000, the digital output value is within the range -4096 to +4095.

(3) Within the analog input and digital output scopes of each input range, the

maximum resolution and accuracy are within the performance specification
range. Outside those scopes, however, they may not fall within the performance
specification range. (Avoid using the dotted line part in Fig. 3.1.)

(4) Set the offset and gain values of the user range setting within the range

satisfying the following conditions.
(a) Setting range when user range setting 1 is selected: -10 to +10V

(b) Setting range when user range setting 2 is selected: 0 to 5V

(c) (Gain value) > (Offset value)

If you attempt to make setting outside the setting range of (a) or (b), the "RUN"
LED flickers at 0.5s intervals.
Set the values within the setting range.
If you attempt to make setting outside the setting range of (c), the "RUN" LED
flickers at 0.5s intervals.
Make setting again.