Electrical service guide for 230 vac model, 9. electrical service guide for 230 vac model – Miller Electric Millermatic 180 User Manual

Page 21

Advertising
background image

.

A complete Parts List is available on-line at www.MillerWelds.com

OM-225 311 Page 17

4-9.

Electrical Service Guide For 230 VAC Model

60 Hz

Single
Phase

Input Voltage

230

Input Amperes At Rated Output

21.7

Max Recommended Standard Fuse Rating In Amperes

Circuit Breaker

1

, Time-Delay

2

25

Normal Operating

3

30

Min Input Conductor Size In AWG

4

14

Max Recommended Input Conductor Length In Feet (Meters)

61

(19)

Min Grounding Conductor Size In AWG

4

14

Reference: 2005 National Electrical Code (NEC) (including article 630)

1 Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.
2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).

4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table

310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.

Y

Caution: Failure to follow these fuse and circuit breaker recommendations could create an electric shock or fire hazard. These
recommendations are for a dedicated branch circuit that applies to the rated output and duty cycle of the welding power source.

4-10. Installing Wire Spool And Adjusting Hub Tension

When a slight force is needed
to turn spool, tension is set.

1/2 in

Tools Needed:

803 012 / 803 013 -B / Ref. 802 444-C

Installing 8 in (203 mm) Wire Spool

Installing 4 in (102 mm) Wire Spool

When a slight force is needed
to turn spool, tension is set.

Retaining ring used

with 8 in (203 mm)

spool only.

Adapter used with

8 in (203 mm)

spool only.

Advertising
This manual is related to the following products: