Fp2499 manual valve – Monessen Hearth DFX24C User Manual

Page 14

Advertising
background image

14

33D4047

DFX & DBX Series Vent Free Fireplaces

FIREPLACE INSTALLATION

When tightening the joint to the valve, hold the valve securely to prevent movement.
Test all gas joints from the gas meter to the heater valve for leaks using a gas analyzer or soap
and water solution after completing connection. DO NOT USE AN OPEN FLAME.
Check the gas pressure with the appliance burning and the control set to HIGH.
Open control access door at bottom front of unit to find valve and regulator referred to below.

W

ARNING

Do not use open flame to check for gas
leaks.

W

ARNING

Connecting directly to an unregulated
propane/LP tank can cause an
explosion.

MANUAL CONTROL

Figure 12
The pressure regulator is preset and locked to discourage
tampering. If the pressure is not as specified, replace the
regulator with the correct part from the parts list in this
manual.
Remove 1/8" NPT plug, located on side of regulator body.
Install fitting and tubing to pressure gauge. After taking
pressure reading, reinstall test plug. Check for gas leaks.

FP2499
manual valve

NPT Test Plug

FP499

Figure 12 -
Pressure Test Point Location
- Manual Control

FP2510
thermostat control

Test Points

FP510

Figure 13 -
Alternate Test Point Location for
Thermostat control Units

THERMOSTAT CONTROL

Figure 13
Turn captured screw counter clockwise two or three turns
and then place tubing to pressure gauge over test point
(Use test point closest to control knob). After taking pres-
sure reading, be sure and turn captured screw clockwise
firmly to reseal. Do not over torque. Check for gas leaks.

MILLIVOLT CONTROL

Figure 14
The valve regulator controls the burner pressure which
should be checked at the pressure test point.

FP2511
millivolt test point

Test Port
'A'

FP511

Figure 14 -
Pressure Test Point Location - Millivolt Valve

Turn captured screw counter clockwise two or three turns
and then place tubing to pressure gauge over test point.
(Use test point “A” closest to gas inlet). After taking pressure
reading, be sure and turn captured screw clockwise firmly
to reseal. Do not over torque. Check for gas leaks.

Advertising