MITSUBISHI ELECTRIC MUZ-GB50VA User Manual

Page 36

Advertising
background image

36

5. Removing outdoor fan motor

(1) Remove the top panel, cabinet and service panel.

(Refer to 1.)

(2) Remove the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Remove the propeller.
(5) Remove the screws fixing the fan motor.
(6) Remove the fan motor.

Photo 7

OPERATING PROCEDURE

PHOTOS

4. Removing the defrost thermistor, discharge temper-

ature thermistor, outdoor heat exchanger tempera-
ture thermistor and ambient temperature thermistor

(1) Remove the top panel, cabinet and service panel.

(Refer to 1.)

(2) Remove the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Pull out the defrost thermistor from its holder. (Photo 6)
(5) Pull out the discharge temperature thermistor from its

holder. (Photo 5)

(6) Pull out the outdoor heat exchanger temperature thermistor

from its holder. (Photo 6)

(7) Pull out the ambient temperature thermistor from its holder.

(Photo 6)

Photo 5

Photo 6

Propeller

Screws of the outdoor fan motor

Discharge temperature thermistor

Defrost
thermistor

Outdoor heat exchanger
temperature thermistor

Ambient
temperature
thermistor

OB455 A--2qxp 06.7.31 2:50 PM Page 36

Advertising