REFRIGERANT SYSTEM DIAGRAM

MUZ-GB50VA

OUTDOOR UNIT

Unit:mm

Outdoor

heat

exchanger

Flared connection

Defrost

thermistor

RT61

Discharge

temperature

thermistor

RT62

Flared connection

Stop valve

Stop valve
(with service port)

Capillary tube

[

3.6

✕[

2.4

50

Refrigerant flow in cooling

Compressor

4-way valve

Refrigerant flow in heating

Refrigerant pipe

[

12.7

(with heat insulator)

Refrigerant pipe

[

6.35

(with heat insulator)

LEV

R.V. coil
OFF
ON

Muffler

#100

Strainer

#100

Receiver

Outdoor heat

exchanger

temperature

thermistor

RT68

Ambient

temperature

thermistor

RT65

Strainer

#100

ADDITIONAL REFRIGERANT CHARGE (R410A:g)

Max. length
A

Max. Height

difference

B

Indoor
unit

Outdoor unit

MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE

Max. length

A

30

Max. Height difference

B

15

Model

Gas

12.7

Liquid

6.35

Piping size O.D : mm

Refrigerant piping : m

MUZ-GB50VA

Model

MUZ-GB50VA

Refrigerant piping length (one way)

Outdoor unit

precharged

1,500

15m

160

20m

260

25m

360

30m

460

7m

0

10m

60

Calculation : Xg=20g/m

(Refrigerant piping length (m)–7)

NOTE : Refrigerant piping exceeding 7m requires additional refrigerant charge according to the calculation.