OM-217 Page 18

3-9.

Electrical Service Guide

60 Hertz Models

70 Ampere Model

100 Ampere Model

Input Voltage

230

460

575

200

230

460

575

Input Amperes At Rated Output

54

27

22

85

74

37

30

Max Recommended Standard Fuse Or Circuit
Breaker Rating In Amperes

80

40

30

125

125

60

45

Min Input Conductor Size In AWG/Kcmil

6

10

10

4

4

8

10

Max Recommended Input Conductor Length In
Feet (Meters)

226

(69)

418

(127)

653

(199)

160

(49)

212

(65)

389

(119)

413

(126)

Min Grounding Conductor Size In AWG/Kcmil

8

10

10

6

6

10

10

Reference: 1993 National Electrical Code (NEC)

S-0092-J

50 Hertz Models

70 Ampere Model

100 Ampere Model

Input Voltage

220

380

415

220

380

415

Input Amperes At Rated Output

57

33

30

77

45

41

Max Recommended Standard Fuse Or Circuit Breaker
Rating In Amperes

80

50

45

125

70

60

Min Input Conductor Size In AWG/Kcmil

6

8

10

4

8

8

Max Recommended Input Conductor Length In Feet
(Meters)

187

(57)

375

(114)

304

(93)

190

(58)

260

(79)

310

(94)

Min Grounding Conductor Size In AWG/Kcmil

8

10

10

6

8

10

Reference: 1993 National Electrical Code (NEC)

S-0092-J