MITSUBISHI ELECTRIC 9800A SERIES UPS User Manual

Page 13

Advertising
background image


MITSUBISHI ELECTRIC 9800A SERIES UPS

MITSUBISHI
ELECTRIC

9800A SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-7

C) Battery operation: Load Power supplied by each system UPS battery and inverter.

FIGURE 1.3 Single Line Diagram - Battery Operation

Referring to Figure 1.3: In the event of AC input source failure or interruption, each
system UPS rectifier will de-energize and each UPS battery will immediately discharge
and supply DC power to the Inverter to maintain continuous AC power to the load. This
operation will continue until:
a) The battery capacity expires and the inverter turns off, or
b) Input power is restored after which the rectifier will power the inverter and critical load

and simultaneously recharge the batteries.


A fully charged battery will provide power for the specified time at the rated load, or longer,
at a reduced load.

When power is restored after a low battery shutdown, each system UPS Rectifier
automatically restarts operation, recharges the batteries and the Inverter is automatically
restarted without operator intervention. Load is automatically assumed by the inverter
without operator intervention.

The power drawn by the load is equally shared between all system UPS during battery
operation.

CB1

Static Transfer

Switch

AC Bypass

Input

AC input

CB

CB3

52S

52C

User supplied
MCCB

UPS Module

Battery cabinet

CB2

Power Flow

Not in Use

RECTIFIER

INVERTER

Output

Advertising