MITSUBISHI ELECTRIC 9800A SERIES UPS User Manual

Page 21

Advertising
background image



MITSUBISHI ELECTRIC 9800A SERIES UPS

MITSUBISHI
ELECTRIC

9800A SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-15

TABLE 1.4 Rating of Contactors and Fuses

OUTPUT CAPACITY OF EQUIPMENT

100kVA 150kVA 225kVA 300kVA 375kVA 500kVA 750kVA

NUMBER APPLICATION

480V

600V

480V

600V

480V 600V

480V 600V

480V

600V

480V

600V

480V

600V

CB1

AC input contactor

135A

200A

350A

450A

660A

660A

910A

CB2 Battery

disconnect

breaker

400A 600A 800A 1200A 1600A

(MEAU)

(MEAU)

CB3 STS

contactor

135A

260A

52C Inverter

output

contactor

135A 200A 350A 450A 450A 660A 910A

52S Bypass

contactor

135A 200A 350A 450A 450A 660A 910A

88RC

Control circuit contactor

90A

FCU, FCV, FCW

AC input fuse

200A/660V

250A/660V

315A/660V

FIU, FIV,

Inverter output fuse 250A/660V 200A/660V 315A/660V 315A/660V 315A/660V 315A/660V 315A/660V

FUA, FUB, FUC

Control power fuse

30A/600V

(OPTION)

FSU, FSV, FSW

Bypass input fuse

200A/

660V

- 315A/

660V

- 250A/

660V

- 250A/

660V

- 315A/

660V

- 315A/

660V

315A/

660V


FZS1, 2, 3

Bypass input ZNR fuse

16A/500V

FBS1, 2, 3

Control power fuse

10A/600V

FZR1, 2, 3

AC input ZNR fuse

16A/500V

F
U

S

E

S

FPU, FPV, FPW

Parallel control

circuit fuse

10A/600V

*Rating would be changed.