Mitsubishi electric – MITSUBISHI ELECTRIC 9800A SERIES UPS User Manual

Page 65

Advertising
background image

MITSUBISHI
ELECTRIC

9800A SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

6-4

MITSUBISHI ELECTRIC 9800A SERIES UPS

UF305

UPS CONTROL CIRCUIT

ERROR

Control clock abnormality

CALL SERVICE

ENGINEER

[2] Major

Lit

on

UF306

UPS CONTROL CIRCUIT

ERROR

Control power source circuit

abnormality

CALL SERVICE

ENGINEER

[2] Major

Lit

on

UF309

INVERTER VOLTAGE

ABNORMAL

Inverter output voltage abnormality

before inverter power supply

CALL SERVICE

ENGINEER

[2] Major

Lit

on

UF352

CONTROL POWER

SUPPLY ABNORMAL

Control circuit abnormality

CALL SERVICE

ENGINEER

[1] Minor

Flicker

UF402 52S

ABNORMAL

52S not turned OFF, or 52S turned

OFF without any command

CALL SERVICE

ENGINEER

[2] Major

Lit

on

UF403 CB3

ABNORMAL

CB3 not turned OFF

(#2)

CALL SERVICE

ENGINEER

[2] Major

Lit

on

UF451 52S

ABNORMAL

52S not turned ON, or 52S turned

ON without any command when

manual transfer

CALL SERVICE

ENGINEER

[1] Minor

Flicker

UF452 CB3

ABNORMAL

CB3

open

CALL SERVICE

ENGINEER

[1] Minor

Flicker

UF453 52L OPERATION ERR.

52L operated abnormality

CHECK 52L

[2]

Major

Lit on

UA801

AC INPUT VOLTAGE OUT

OF RANGE

AC input voltage fell out of +/- 15%

range

CHECK INPUT

POWER

SOURCE

[1] Alarm -

UA806

INVERTER OVERLOAD

> 100%

Overload exceeded 105% (Note 7)

WARNING :

DECREASE

LOAD

[1] Alarm -

UA808

INVERTER OVERLOAD

> 125%

Overload exceeded 125% (Note 7)

WARNING :

DECREASE

LOAD

[1] Alarm -

UA809

INVERTER OVERLOAD

> 150%

Overload exceeded 150% (Note 7)

WARNING :

DECREASE

LOAD

[1] Alarm -

UA810 INVERTER

OVERLOAD

Momentary over-current during

Inverter power.

WARNING :

DECREASE

LOAD

[1] Alarm -

UA811 OVERLOAD

TRANS.

Overload

transfer

-

[1]

Alarm

UA812

BYPASS VOLTAGE OUT

OF RANGE

Bypass voltage fell out of +/- 20%

range

CHECK

BYPASS INPUT

[1] Alarm -

UA813

BYPASS PHASE

ROTATION ERROR

Phase rotation is inverted when

bypass voltage is normal

CHECK

BYPASS INPUT

[1] Alarm -

UA814

BYPASS FREQUENCY

OUT OF RANGE

Bypass frequency fell out of

inverter synchronization follow-up

range

CHECK

BYPASS INPUT

[1] Alarm -