MITSUBISHI ELECTRIC 9800A SERIES UPS User Manual

Page 38

Advertising
background image


MITSUBISHI ELECTRIC 9800A SERIES UPS

MITSUBISHI
ELECTRIC

9800A SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

3-5

TABLE 3.4 Recommended Cable Sizes

Input Side * 1, 2

Output Side * 1, 2

Bypass Side * 1, 2

DC Input Side * 1, 2

kVA

Capacity

Input

Voltage

Output

Voltage

Cable

Size

Torque

in. lbs

Cable

Size

Torque

in. lbs

Cable

Size

Torque

in. lbs

Cable

Size

Torque

in. lbs

100kVA

480V

480V

1 AWG

or larger

200 - 269

in. lbs

1 AWG

or larger

200 - 269

in. lbs

1 AWG

or larger

200 - 269

in. lbs

3/0 AWG

or larger

200 - 269

in. lbs

600V 600V 2

AWG

or larger

200 - 269

in. lbs

2 AWG

or larger

200 - 269

in. lbs

2 AWG

or larger

200 - 269

in. lbs

3/0 AWG

or larger

200 - 269

in. lbs

150kVA

480V

480V

3/0 AWG

or larger

347 - 469

in. lbs

3/0 AWG

or larger

347 - 469

in. lbs

3/0 AWG

or larger

347 - 469

in. lbs

350 MCM

or larger

347 - 469

in. lbs

600V 600V 2/0

AWG

or larger

347 - 469

in. lbs

2/0 AWG

or larger

347 - 469

in. lbs

2/0 AWG

or larger

347 - 469

in. lbs

350 MCM

or larger

347 - 469

in. lbs

225kVA

480V

480V

300 MCM

or larger

347 - 469

in. lbs

350 MCM

or larger

347 - 469

in. lbs

350 MCM

or larger

347 - 469

in. lbs

2x4/0 AWG

or larger

347 - 469

in. lbs

600V 600V 250

MCM

or larger

347 - 469

in. lbs

250 MCM

or larger

347 - 469

in. lbs

250 MCM

or larger

347 - 469

in. lbs

2x4/0 AWG

or larger

347 - 469

in. lbs

300kVA

480V

480V

2x4/0 AWG

or larger

347 - 469

in. lbs

2x3/0 AWG

or larger

347 - 469

in. lbs

2x3/0 AWG

or larger

347 - 469

in. lbs

2x400 MCM

or larger

347 - 469

in. lbs

600V 600V 2x3/0

AWG

or larger

347 - 469

in. lbs

400 MCM

or larger

347 - 469

in. lbs

400 MCM

or larger

347 - 469

in. lbs

2x400 MCM

or larger

347 - 469

in. lbs

375kVA

480V

480V

3x300 MCM

or larger

347 - 469

in. lbs

2x250 MCM

or larger

347 - 469

in. lbs

2x250 MCM

or larger

347 - 469

in. lbs

3x350 MCM

or larger

347 - 469

in. lbs

600V 600V 2x4/0

AWG

or larger

347 - 469

in. lbs

2x3/0 AWG

or larger

347 - 469

in. lbs

2x3/0 AWG

or larger

347 - 469

in. lbs

3x350 MCM

or larger

347 - 469

in. lbs

500kVA 480V 480V 3x250

MCM

or larger

347 - 469

in. lbs

2x400 MCM

or larger

347 - 469

in. lbs

2x400 MCM

or larger

347 - 469

in. lbs

3x500 MCM

or larger

347 - 469

in. lbs

600V

600V

2x350

MCM

or larger

347 – 469

in. lbs

2x300 MCM

or larger

347 - 469

in. lbs

2x300 MCM

or larger

347 - 469

in. lbs

3x500 MCM

or larger

347 - 469

in. lbs

750kVA 480V 480V 3x500

MCM

or larger

347 - 469

in. lbs

3x500 MCM

or larger

347 - 469

in. lbs

3x500 MCM

or larger

347 - 469

in. lbs

5x500 MCM

or larger

347 - 469

in. lbs

600V 600V 3x350

MCM

or larger

347 - 469

in. lbs

3x350 MCM

or larger

347 - 469

in. lbs

3x350 MCM

or larger

347 - 469

in. lbs

5x500 MCM

or larger

347 - 469

in. lbs


*1 - The cables must be selected to be equal to or larger than the sizes listed in the table.
*2 - Voltage drop across power cables not to exceed 2% of nominal source voltage.
*3 - Allowable ampere-capacities based on 90゚C insulation at ambient temperature of 30゚C.
Not more than 3 conductors in a raceway without de-rating.

Note: Copper conductors assumed.

Advertising