OWNERS / TECHNICAL MANUAL

Page Number:

3-1


3.0 INSTALLATION AND OPERATION

3.1 Transportation and Installation

TABLE 3.1 How to transport and install the system

Transportation

Installation

Transport unit with forklift.
Carry with overhead crane using
eyebolts provided.

Using the pre drilled holes (4 - 24) in the
UPS channel base, anchor the unit using
appropriate hardware. (Not provided)

Note :

Do not transport in a horizontal position. Cabinets must be maintained

upright within +/- 15° of the vertical during handling

.

3.2 Installation Procedure

A) Note the load tolerance of the floor

Refer to Table 3.2 for list of UPS weights.

TABLE 3.2 List of UPS weights

UPS Capacity (kVA)

100

150

225

300

375

500

750

Weight

(lb.)

2100 2820 3310 4990 5250 6930 9655

B) Minimum clearance required for ventilation

Right side

25 mm (not required when sidecars are used)

Left side

25 mm (not required when sidecars are used)

Back side

0.0 mm

Top side

600 mm (for air flow)

C) Space requirement for routine maintenance

Allow for the following space at the time of installation.
Front

1000 mm 100kVA, 150kVA, 225kVA

1075 mm 300kVA, 375kVA, 500kVA, 750kVA
Sides

0.0 mm

Rear

0.0 mm