D) External Battery Supply

Please refer to the following when installing and maintaining batteries:

1. The customer shall refer to the battery manufacturer's installation manual for

battery installation and maintenance instructions.

2. The maximum permitted fault current from the remote battery supply, and the

DC voltage rating of the battery supply over-current protective device are
shown in Table 3.3.

TABLE 3.3 Maximum Permitted Fault Current

UPS CAPACITY

(kVA)

DC VOLTAGE

RATING (V)

MAXIMUM PERMITTED

FAULT CURRENT (A)

100 480 25000

150 480 25000

225 480 25000

300 480 25000

375 480 25000

500 480 25000

750 480 25000

3.3 Procedure for Cable Connections *

i.

Confirm the capacity of the UPS being installed. Identify the input/output power

terminal blocks as shown in the appropriate Figures 3.1 through 3.2-a~g,Figure 3.3. and

Figure 3.4a~c. (Note *

Figure

3.4a~c

shows power and control wire for parallel system.)

ii.

Connect the internal control wire and power wire.

(1) Control wire Inter-connect

1. CB2 Auxiliary to terminal 1, 2.
2. CB2-UVT to terminal 3, 4.
3. Parallel configuration Wiring (Refer to Figure 3.4a~c )

- CLC CB 52L1-AX, 52L2-AX …. 52Ln-AX to UPSn TB1 (1,2 terminals)
- Parallel Control CN92, CN93, In, Out cables between UPS modules

(2) Power wire Inter-connect

a.) From user’s distribution panel

1. X1 (A-phase) to A bus bar in UPS rectifier section.
2. X2 (B-phase) to B bus bar in UPS rectifier section.
3. X3 (C-phase) to C bus bar in UPS rectifier section.