EPS 7000 Shared Systems

page 2 —10

UPS INPUT PROBLEM

CHECK FREQUENCY !

This message indicates that the main AC input (mains 1) frequency is out of tolerance. The rectifier/battery charger

has shut down and the inverter is operating from its battery source.

UPS INPUT PROBLEM

CHECK VOLTAGE !

This message indicates that the main AC input (mains 1) voltage is out of tolerance. the rectifier/battery charger

has shut down and the inverter is operating from its battery source.

CHARGER SHUTDOWN

COMMAND ON !

This message indicates that the rectifier/battery charger has been instructed to shut down, for example during

progressive (stepped) transfer to a motor-generator set.

INPUT KVA LIMITED

COMMAND ON !

This message indicates that the rectifier/battery charger has been instructed to limit the power drawn from the main

AC input (mains 1) source. This condition occurs, for example, when the load is being supplied by an undersized

motor-generator set; the UPS battery source is called upon to make up the difference.

BATTERY CURRENT

LIMIT COMMAND ON !

This message indicates that the rectifier/battery charger has been instructed to limit the charge current to the

battery. Normal charge current to the battery will be supplied when the command is released. This condition occurs,

for example, when the load is being supplied by an undersized motor-generator set.

QF1 BATTERY BREAKER

OPEN !

This message indicates that the battery circuit breaker QF1 has been opened or has tripped. the load is no longer

protected, since battery power is unavailable.

LOW BATTERY

. . . !

This message indicates that the inverter has shut down, due to depletion of the battery’s stored energy.

CHARGER OFF

. . . !

This message indicates that the rectifier/battery charger has shut down.