CHARGER FAULT

CALL SERVICE !

This message indicates that a fault has occurred in the rectifier/battery charger, and that service is required.

Q1 UPS INPUT CB

OPEN !

This message indicates that the input isolation circuit breaker is open or has tripped. It must be closed for

rectifier/battery charger start-up.

INVERTER OVERLOAD

CHECK P.F. AND KW

This message indicates that the inverter is in an overload condition, usually due to excessive real power (kW) being

drawn by the load. The flashing “KW” indicates that the operator should check the load real power. The inverter

will keep supplying the load for a certain amount of time depending on the overload level.

INVERTER FAULT

CALL SERVICE !

This message indicates that a fault has occurred in the inverter, and that service is required.

INVERTER SHUTDOWN

OVERLOAD > I MAX!

This message indicates that an overload greater than 1.5 times the full power rating of the inverter has occurred,

and that the inverter has shut down.

INVERTER SHUTDOWN

THERMAL OVERLOAD A

This message indicates that an overload below 1.5 times the full power rating of the inverter has occurred and that

the inverter has shut down. The flashing “A” indicates that the operator should check the load current.

I LOAD > IN

CHECK LOAD A

This message indicates that the load power being drawn is greater than the UPS full load rating. The flashing “A”

indicates that the operator should check the load current. The inverter or static switch will keep supplying the load

for a certain amount of time depending on the overload level.

TRANSFER FAULT

CALL SERVICE !

This message indicates that a fault has occurred that affects the transfer of the load between the inverter and the

bypass source. Service is required.