cx400/px400 Sub. pump • operation and partS manual — rev. #1 (12/03/10) — page 19

connecting dual float Switch (SW-1Wop) to

control box

1. Remove the float switch input connector housing, then

route the float switch wires through the cable gland on

the control box. Attach the wires of the float switch to

the terminal block as indicated by Table 5 and Figure 10.

2. Tighten the connector housing to ensure a tight fit

between the cord and the connector body. This will

prevent the cable from pulling out of the terminal block

and also prevent moisture from entering the control

box.

3. Determine the tether length of the float switch wires

then secure float switch wires to pump discharge hose.

See Figure 8 or Figure 9 and Table 3 to determine the

pumping range.

connecting ac power to the cb3 control box

1. The AC input power cord (not included) should have

three wires. Each wire is color coded. The colors are

WHite, blacK and green.

2. Remove the AC input connector housing from the

control box, then route the power cord through the

cable gland on the control box.

3. Connect the AC input power cord to the contactor

located inside the control box as shown in Figure 10,

and Table 6.

Table 5. dual Float switch connections

Float

Switch

Terminal

block no.

Wire

Color

Start

TB1-A1
TB1-A2

Black

White

Stop

TB1-B8
TB1-B7

Black

White

Table 6. 1Ø-115 vac power

Connections

Wire Color

Contactor.

BLACK

L1

WHITE

L2

GREEN

GROUND

OperatiOn

4. Connect the other end of the AC power cord to the

voltage source. Remember to provide a means of

disconnecting the power from the control box (circuit

breaker or quick disconnect switch). Also make sure

to provide a good earth ground to the control box

Connecting AC Power to the Pump Motor

1. AC power is routed to the pump motor via a contactor.

The coil of the contactor is energized or de-energized

by the opening and closing of the float switch contacts.

2. The power cord (included with pump) should have three

wires. Each wire is color coded. The colors are

WHite,

blacK and green.

3. Remove the pump AC input connector housing from

the control box, then route the power cord through the

cable gland on the control box.

4. Connect pump power cord to the contactor as shown

in Figure 10, and Table 7.

NOTICE

It is recommended that the power being supplied to the

control box

alWaYS be connected to a circuit breaker

or a

quick disconnect switch. This safety feature

allows for quick removal of power from the control box

in the event of an emergency.

table 7. ac output power

Connections To Pump

Wire Color

contractor

BLACK

T1

WHITE

T2

GREEN

Ground