Page 17 801P5 Smart Switch

TM

NOTE

PROGRAMMING MODE

In Programming Mode, you can:

Change the set points

Perform field pressure calibration

Program Window or Standard Mode

Change the password

Program display update time

Program delays for both switches

Scale the readout

Reset the Smart-Switch

TM

to factory defaults

If your unit includes the 4-20 mA option, you can:

Activate 4-20 mA mode

Calibrate the 4-20 mA

Scale the 4-20 mA output

If your unit includes the RS232 option, you can:

Set the BAUD rate

The unit will not function as a switch while in programming
mode.

ENTER PROGRAMMING MODE

To access the programming mode, press the [MENU] key (See
Figure 7). On the initial startup, no password is required. If you
have previously set up a password, you must enter it at this time:

1. When the displays show ---O, press the [UP/DOWN

ARROW] keys to set the first digit.

2. Press [SELECT] to move to the next digit.

3. Repeat this process until display shows the correct password.

4. Press [STORE] to enter programming mode.