ITT SMART SWITCH 801P5 User Manual

Page 34

Advertising
background image

Page 30 Installation and Operation Manual

Display Shows EROR

This message might appear while programming the 801P5
Smart-Switch

TM

. The meaning depends on what is being

programmed. Following are the possible causes and solutions.

Incorrect password entered

You have entered an incorrect password. Re-enter the
correct password. If you have lost or forgotten the password,
contact Neo-Dyn Customer Service for assistance.

Incompatible switch set points.

You have entered incompatible set points. Switch 1 and
Switch 2 are independent of each other; however, the
following rules apply to each switch:

The increasing set point must be at or below the Full Scale
Output (F.S.O.) value; it cannot be less than 2% of F.S.O.,
and it must be at least 1% of F.S.O. above the decreasing set point.

The decreasing set point must be no lower than 1% of
F.S.O.; it can be no higher than 99% of F.S.O.; and it must
be at least 1% of F.S.O. below the increasing set point.

The minimum deadband is 1% of F.S.O.

Re-enter the set points to conform to the requirements.

Advertising