Page 26 Installation and Operation Manual

NOTE

4-20 MILLIAMPERE OUTPUT CALIBRATION (4CAL)

The 801P5 is factory calibrated to generate 4 mA when the
pressure sensor is at 0 psig, and 20 mA when rated pressure is
applied. Tolerances in your signal conditioning equipment may
result in readings varying from these values, so you can calibrate
the 4-20 mA output as follows to correct these readings.

1. Connect a calibrated milliammeter to the 4-20 mA output.

2. Press [MENU], then press the [UP/DOWN ARROW] key

until 4CAL is displayed.

3. Press [SELECT]. The display will show LO-C.

4. While reading the milliammeter, use the [UP/DOWN

ARROW] keys to adjust the output to 4 milliamperes.

5. Press the [STORE] key. The display will read HI-C.

6. Use the [UP/DOWN ARROW] keys to adjust the output to

20 mA, then press the [STORE] key to temporarily save the
calibration data and return to the main menu.

7. Press [RUN] and [SELECT] to save the changes and return

online.

If the 0 or Full Scale output has shifted by 4% of F.S.O. or more
from the factory calibration, EROR will be displayed.