Online power – IBM Fire Alarm Back-up UPS1481 UNIT User Manual

Page 22

Advertising
background image

OnLine Power

(6002-1646) REV.X8

16

3.

Determine which signals will be used. Connect wires (customer-supplied) to the connector.


4.

This concludes the remote signaling connection procedures.


5.

This concludes the installation procedures. Please proceed to Section 3-Start-Up for these
necessary to start- up the Fire Alarm Back-up UPS1481.



2-3-2 RS232

Connection


Control

PCBD

J8 – connector / P8 IBM PC Serial Port

J2 – connector / P8 to 2  to 2

J3 – connector / P8 to 3  to 3

J5 – connector / P8 to 5  to 5


Pin 1, 4, 6, 7, 9 no connection


Pin

2

:

Receive

Pin

3

:

Transmit

Pin

5

:

GND



2-4 Storage

The Fire Alarm Back-up UPS1481 Series can be placed in storage while not in use. Provide a
protected environment which meets the environmental parameters listed below.

• AMBIENT TEMPERATURE -22° to 158°F

-30°

to

70°C

RELATIVE

HUMIDITY 0%

to

95%

non-condensing


The Fire Alarm Back-up UPS1481 Series will be stored for several months or longer, it should
be serviced by charging the batteries for 24 hours at regular, three-month intervals. While in
storage, service the unit using the procedures in this section.


AS400 CONNECTION DETAILS (J2)

K1

K2

K3

K4

9

8

7

6

5

INPUT FAIL

LOW BATT.

SUM-ALARM

BYPASS ON

COMMON