Online power – IBM Fire Alarm Back-up UPS1481 UNIT User Manual

Page 34

Advertising
background image

OnLine Power

(6002-1646) REV.X8

28

INPUT CIRCUIT BREAKER


TABLE B-3: Input Breaker Ampacity (Standard KAIC)

Input Voltages

KVA

120 Vac

240 V/ or 208V

3

50 Amps, 120 VAC,

1 Pole, 14 KAIC

OLP P/N: 2025-784

30 Amps, 240 VAC,

2 Pole, 14 KAIC

OLP P/N: 2025-790

5

70 Amps, 120 VAC,

1 Pole, 14 KAIC

OLP P/N: 2025-997

40 Amps, 240 VAC,

2 Pole, 10 KAIC

OLP P/N: 2025-791

7.5 N/A

60 Amps, 240 VAC,

2 Pole, 10 KAIC

OLP P/N: 2025-793

10 N/A

70 Amps, 240 VAC,

2 Pole, 10 KAIC

OLP P/N: 2025-794

12.5 N/A

90 Amps, 240 VAC,

2 Pole, 10 KAIC

OLP P/N: 2025-796

15 N/A

125 Amps, 240 VAC,

2 Pole, 65 KAIC

OLP P/N: 2025-759

TABLE B-4: Input Breaker Ampacity (hIGH KAIC)

Input Voltages

KVA

120 Vac

240 Vac or 208VAC

3

50 Amps, 120 VAC,

1 Pole, 42 KAIC

OLP P/N: 2025-800

30 Amps, 240 VAC,

2 Pole, 65 KAIC

OLP P/N: 2025-764

5

70 Amps, 120 VAC,

1 Pole, 42 KAIC

OLP P/N: 2025-998

40 Amps, 240 VAC,

2 Pole, 65 KAIC

OLP P/N: 2025-766

7.5 N/A

60 Amps, 240 VAC,

2 Pole, 65 KAIC

OLP P/N: 2025-768

10 N/A

70 Amps, 240 VAC,

2 Pole, 65 KAIC

OLP P/N: 2025-769

12.5 N/A

90 Amps, 240 VAC,

2 Pole, 65 KAIC

OLP P/N: 2025-771

15 N/A

125 Amps, 240 VAC,

2 Pole, 65 KAIC

OLP P/N: 2025-759